| Plan Review Notes For Permit 15080951 |
| Permit Number |
15080951 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-09-11 14:54:00 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE SIGNED AND SEALED RAS 117 CALCULATIONS FOR | | | ENHANCED FASTENING FROM A LICENSED DESIGN PROFESSIONAL | | | THAT WERE SUBMITTED ARE FOR NOA NO.13-1022.15 WHICH IS | | | NOT THE PRODUCT APPROVAL THAT WAS SUBMITTED ( NOA NO. | | | 14-0611.01 ). FBC 107.2.1.3 | | | |
|