2015-10-07 15:14:52PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC ENERGY CONSERVATION - SECT. 403.6.1 EQUIPMENT
 SIZING.
 HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN
 ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT
 LOADS CALCULATED IN ACCORDANCE WITH MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES,
 BASED ON BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION
 OF THE BUILDING. THE MANUFACTURER AND MODEL NUMBER OF
 THE OUTDOOR AND INDOOR UNITS (IF SPLIT SYSTEM) SHALL BE
 SUBMITTED ALONG WITH THE SENSIBLE AND TOTAL COOLING
 CAPACITIES AT THE DESIGN CONDITIONS DESCRIBED IN
 SECTION 302.1. THIS CODE DOES NOT ALLOW DESIGNER SAFETY
 FACTORS, PROVISIONS FOR FUTURE EXPANSION OR OTHER
 FACTORS WHICH AFFECT EQUIPMENT SIZING. SYSTEM SIZING
 CALCULATIONS SHALL NOT INCLUDE LOADS CREATED BY LOCAL
 INTERMITTENT MECHANICAL VENTILATION SUCH AS STANDARD
 KITCHEN AND BATHROOM EXHAUST SYSTEMS.
  
 2) FBC-R - M 1602.4 PROVIDE BALANCED AIR RETURN AT
 BEDROOMS. TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING
 THE RETURN TRANSFER 11/2 TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM OR
 SPACE IT IS SERVING AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCH (25 MM) UNDERCUT TO ACHIEVE PROPER
 RETURN AIR BALANCE. HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR PROPER BALANCED
 RETURN AIR EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS
 AND LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE
 MASTER SUITE SHALL BE INCLUDED. THERE IS ONE 8" AND TWO
 4" SUPPLY DUCTS IN THE MASTER SUITE. THE 10" TRANSFER
 DUCT IS TOO SMALL.
  
 3) SPECIFY THE LOCATION OF THE LOCATION AND SIZE OF THE
 RETURN AIR ON THE PLANS. FBCR - M1602.2
  
 4) M1506.2 EXHAUST OPENINGS. (BATHROOM) AIR EXHAUST
 OPENINGS SHALL TERMINATE NOT LESS THAN 3 FEET (914 MM)
 FROM PROPERTY LINES; 3 FEET (914 MM) FROM OPERABLE AND
 NONOPERABLE OPENINGS INTO THE BUILDING AND 10 FEET
 (3048 MM) FROM MECHANICAL AIR INTAKES EXCEPT WHERE THE
 OPENING IS LOCATED 3 FEET (914 MM) ABOVE THE AIR
 INTAKE.
  