| 2015-08-27 07:00:49 | 1ST REVIEW: FBC 2014 MECHANICAL |
| | PERMIT #15080942 |
| | 8/27/15 |
| | |
| | 1) SUBMIT TWO SETS OF AC LOAD CALCULATIONS FOR THE NEW |
| | MINI-SPLIT SYSTEM- SEE SECTION C403.2.1 FBC-14 ENERGY |
| | CONSERVATION: CALCULATION OF HEATING AND COOLING LOADS. |
| | DESIGN LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE |
| | PROCEDURES DESCRIBED IN THE ASHRAE/ACCA STANDARD 183 OR |
| | ACCA MANUAL N AND SHALL BE ATTACHED TO THE CODE |
| | COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT |
| | WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE |
| | MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE |
| | SIZING CALCULATION SHALL BE SUBMITTED WITH THE |
| | APPLICATION FOR THE MECHANICAL PERMIT. HEATING AND |
| | COOLING LOADS SHALL BE ADJUSTED TO ACCOUNT FOR LOAD |
| | REDUCTIONS THAT ARE ACHIEVED WHEN ENERGY RECOVERY |
| | SYSTEMS ARE UTILIZED IN THE HVAC SYSTEM IN ACCORDANCE |
| | WITH THE ASHRAEHVAC SYSTEMS AND EQUIPMENT HANDBOOK. |
| | ALTERNATIVELY, DESIGN LOADS SHALL BE DETERMINED BY AN |
| | APPROVED EQUIVALENT COMPUTATION PROCEDURE, USING THE |
| | DESIGN PARAMETERS SPECIFIED IN CHAPTER 3. |
| | 2) PROVIDE A PLAN SHOWING THE LOCATIONS OF THE OUTDOOR |
| | AND INDOOR UNITS AND INCLUDE TIE DOWN ENGINEERING FOR |
| | THE CONDENSER, AND A CONDENSATE DISPOSAL PLAN FOR THE |
| | AIR HANDLER- SECTION 301.15 AND 307 FBC-14 MECHANICAL. |
| | 3) PROVIDE AN ELECTRICAL PLAN AND SUB-PERMIT. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |