| Plan Review Notes For Permit 15080892 |
| Permit Number |
15080892 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-08-29 11:07:49 | ****CORRECTIONS**** | | | REVISED 9/16 | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. PROVIDE A PLAN SHOWING LOCATION OF PROPOSED DOORS, | | | FIRE RATING OF PROPOSED DOORS, AND FIRE RATING FOR THE | | | WALLS. | | | | | | NOT ENOUGH INFORMATION WAS PROVIDED TO PERFORM A PLAN | | | REVIEW, FBC 107. | | | | | | PLAN SHOULD SHOW LOCATION OF DOORS, ALL FIRE RATED | | | WALLS (ALL APPLICABLE SEPARATIONS SUCH AS FIRE PUMP | | | ROOMS, ELECTRICAL ROOMS, STORAGE AS WELL AS OCCUPANCY | | | SEPARATION, ETC.). SEE FBC CHAPTERS 5, 7. | | | | | | 2. FBC 107, THE PLAN IS TO INCLUDE THE PRINTED NAME AND | | | SIGNATURE OF THE INDIVIDUAL TAKING RESPONSIBILITY FOR | | | THE INFORMATION AND DESIGN. A DESIGN PROFESSIONAL MAY | | | BE REQUIRED, FS471, 481.229(C). | | | | | | 3. IF ANY DOORS ARE EXTERIOR DOORS, AND IF THE BUILDING | | | IS GREATER THAN 60FEET, DESIGN PRESSURES TO BE | | | DETERMINED BY A DESIGN PROFESSIONAL, FBC 1609 | | | (ASCE7-10), FS 471, 481. | | | | | | |
|