| Plan Review Notes For Permit 15080889 |
| Permit Number |
15080889 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-10-05 11:06:36 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) / 2011 NEC | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY ELECTRICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) NEC 240.24(A) - (F) PANELS SHALL BE READILY | | | ACCESSIBLE. SPECIFY THE LOCATION OF THE PANEL ON THE | | | ELECTRICAL FLOOR PLAN. | | | | | | 2) NEC 110.26 SUFFICIENT ACCESS AND WORKING SPACE SHALL | | | BE PROVIDED AND MAINTAINED ABOUT ALL ELECTRICAL | | | EQUIPMENT TO PERMIT READY AND SAFE OPERATION AND | | | MAINTENANCE OF SUCH EQUIPMENT. SPECIFY THE LOCATION OF | | | THE SERVICE (METER) ON THE ELECTRICAL FLOOR PLAN. | | | | | | 3) NEC 440.11 & 440.14 SHOW THE LOCATION OF THE | | | REQUIRED A/C EQUIPMENT DISCONNECTING MEANS ON THE | | | PLANS. | | | | | | 4) NEC 210.11 (C) (3) AT LEAST ONE 20 - AMP BRANCH | | | CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE | | | OUTLETS. | | | | | | 5) THE ELECTRICAL DESIGN CODE NOTE INCORRECTLY | | | REFERENCES THE 2008 NEC. THE FIFTH EDITION 2014 FBC | | | REFERENCES THE 2011 NEC. |
|