Plan Review Notes
Plan Review Notes For Permit 15080879
Permit Number 15080879
Review Stop G
Sequence Number 2
Notes
Date Text
2015-09-15 05:08:201) THE GAS LINE TO THE FIRE PIT IS SHOWN AS PE PIPE AND
 ALSO AS CSST. I CANNOT TELL ON THE DRAWING WHERE THE
 TRANSITION TAKES PLACE. CLARIFY.
 2) INDICATE ON THE PLANS THE SIZE OF THE CONDUIT SLEEVE
 AND THE TYPE OF PIPING AND THAT THE INSTALLATION
 COMPLIES WITH 2014 FBC-FUEL GAS SEC.404.14.1, 404.14.2,
 404.14.PLEASE NOTE: PIPING UNDERGROUND BENEATH
 BUILDINGS IS PROHIBITED UNLESS THERE IS NO OTHER WAY TO
 INSTALL THE PIPING. FGC SEC.404.14.
 3) SUBMIT MANUF. SPECS FOR THE GAS HOSE TO THE BBQ
 GRILL. THE HOSE SHALL BE LISTED FOR USE WITH LP GAS.
 4) SHOW THE SIZE OF THE LINE DOWNSTREAM OF THE PRESSURE
 REGULATOR FOR THE POOL HEATER.THE FUTURE LINE FOR THE
 POOL HEATER SHALL BE VALVED AND CAPPED.
 5) INDICATE THE SIZE AND TYPE OF PIPE FROM THE
 REGULATOR AT THE TANK TO THE REGULATOR FOR THE FIRE PIT
 & BBQ AND FROM THE TANK REGULATOR TO THE GENERATOR.