| Plan Review Notes For Permit 15080879 |
| Permit Number |
15080879 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-08-27 13:34:21 | 1) THE HIGH PRESSURE THAT WAS SUBMITTED IS FROM AN | | | OUTDATED EDITION OF THE GAS CODE AND IS NOT | | | ACCEPTABLE.SUBMIT A COPY OF A CURRENT SIZING TABLE FOR | | | THE HIGH PRESSURE SIDE. WPB AMEND. TO FBC SEC. 107.2.1. | | | 2) SUBMIT 2 COPIES OF MANUFACTURER'S SPECIFICATION | | | SHEETS FOR ALL GAS APPLIANCES. APPLIANCES SHALL BE | | | LISTED AND LABELED PER THE 2014 FBC-R, SEC. G2404.3. | | | 3) REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING | | | SHALL BE APPROVED FOR OUTDOOR INSTALLATION. 2014 FBC-R | | | SEC.G2421.1. | | | 4) SHOW THE LENGTH OF EACH SECTION OF PIPE FOR THE LOW | | | PRESSURE SYSTEM FROM THE REGULATOR TO THE APPLIANCE AND | | | THE TYPE OF PIPE. | | | 5) CLEARLY SHOW THE BTU LOAD OF EACH APPLIANCE. SOME OF | | | THE VALUES ARE VERY HARD TO READ. | | | 6) THE TANK ANCHORING DETAIL FORM PLAN CITY STEEL CO. | | | IS ILLEGIBLE. SUBMIT 2 CLEAR COPIES FOR REVIEW. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|