Plan Review Notes
Plan Review Notes For Permit 15080879
Permit Number 15080879
Review Stop G
Sequence Number 1
Notes
Date Text
2015-08-27 13:34:211) THE HIGH PRESSURE THAT WAS SUBMITTED IS FROM AN
 OUTDATED EDITION OF THE GAS CODE AND IS NOT
 ACCEPTABLE.SUBMIT A COPY OF A CURRENT SIZING TABLE FOR
 THE HIGH PRESSURE SIDE. WPB AMEND. TO FBC SEC. 107.2.1.
 2) SUBMIT 2 COPIES OF MANUFACTURER'S SPECIFICATION
 SHEETS FOR ALL GAS APPLIANCES. APPLIANCES SHALL BE
 LISTED AND LABELED PER THE 2014 FBC-R, SEC. G2404.3.
 3) REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING
 SHALL BE APPROVED FOR OUTDOOR INSTALLATION. 2014 FBC-R
 SEC.G2421.1.
 4) SHOW THE LENGTH OF EACH SECTION OF PIPE FOR THE LOW
 PRESSURE SYSTEM FROM THE REGULATOR TO THE APPLIANCE AND
 THE TYPE OF PIPE.
 5) CLEARLY SHOW THE BTU LOAD OF EACH APPLIANCE. SOME OF
 THE VALUES ARE VERY HARD TO READ.
 6) THE TANK ANCHORING DETAIL FORM PLAN CITY STEEL CO.
 IS ILLEGIBLE. SUBMIT 2 CLEAR COPIES FOR REVIEW.
  