| Plan Review Notes For Permit 15080857 |
| Permit Number |
15080857 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-08-26 08:39:07 | APPROVED WITH EXCEPTION. THIS PLAN HAS BEEN APPROVED | | | PROVISIONALLY. FAILURE TO CORRECT THE LISTED | | | DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION WILL | | | RESULT IN FAILED INSPECTION(S) AND ASSESSMENT OF | | | RE-INSPECTION FEE(S). | | | 1) PROVIDE AT LEAST ONE GFCI PROTECTED RECEPTACLE | | | LOCATED A MINIMUM OF 6 FEET FROM AND NOT MORE THAN 20 | | | FEET FROM THE INSIDE WALL OF THE POOL. FBCR - E4203.1.2 | | | | | | 2) BOND ALL FIXED METAL PARTS WITHIN 5 FEET OF THE | | | INSIDE WALL OF THE POOL. FBCR - E4204.2 (7) | | | | | | 3) POOL WATER SHALL BE INTENTIONALLY BONDED IN | | | ACCORDANCE WITH INSIDE WALL OF THE POOL. FBCR - E4204.3 |
|