| 2015-12-07 17:46:59 | RESIDENTIAL (R3) ADDITION/ALTERATION, SECOND BUILDING |
| | REVIEW CHECKLIST. |
| | CODE: FBC-5TH EDITION (2014). |
| | |
| | NOTE: |
| | SEE ZONING COMMENTS REGARDING BUILDING SETBACKS. IN |
| | ADDITION, SEE COMMENTS BELOW. |
| | |
| | 1- BASED ON SURVEY SUBMITTED, THE ADDITION IS LOCATED |
| | LESS THAN 3'-0" FROM THE PROPERTY LINE. NEED TO COMPLY |
| | WITH THE FOLLOWING: |
| | A) NO OPENINGS ALLOWED. SEC. R302.1 AND TABLE R302.1(1) |
| | OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | B) NEED TO SPECIFY 1 HR FIRE RATED EXTERIOR WALL |
| | ASSEMBLY. SPECIFY PUBLISHED ASSEMBLY NUMBER. ASSEMBLY |
| | SPECIFIED TO BE TESTED IN ACCORDANCE WITH ASTM E 119 OR |
| | UL 263 WITH EXPOSURE ON BOTH SIDES. SEC. R302.1 AND |
| | TABLE R302.1(1) OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | C) SPECIFY 1 HR FIRE RATED ASSEMBLY FOR THE UNDERSIDE |
| | OF THE ROOF PROJECTION AS REQUIRED BY SEC. R302.1 AND |
| | TABLE R302.1(1) OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | D) WALL PENETRATIONS NEED TO COMPLY WITH SEC. R302.1 |
| | AND TABLE R302.1(1) OF FBC-RESIDENTIAL, 5TH EDITION |
| | (2014). |
| | |
| | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) EXTERIOR DOOR. PROVIDE THE FLORIDA PRODUCT APPROVAL |
| | COVER PAGE THAT CORRESPONDS TO DOOR DRAWINGS SUBMITTED. |
| | NOTE: NEED FLORIDA PRODUCT APPROVAL COVER PAGE FOR 2014 |
| | CODE. |
| | RESPONSE: PRODUCT APPROVAL INFORMATION SUBMITTED |
| | DOESN'T HAVE A FLORIDA PRODUCT APPROVAL COVER PAGE OR |
| | FLORIDA PRODUCT APPROVAL NUMBER THAT CORRESPONDS TO |
| | DRAWINGS SUBMITTED. AND, DRAWINGS SUBMITTED DON'T MATCH |
| | TYPE OF DOOR SHOWN ON PLANS. |
| | |
| | B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON ALL |
| | DETAILS. PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE |
| | AND PAGE SHOWING THE SPECIFIED CONNECTOR OR ENGINEER TO |
| | LIST THE 2014 FLORIDA PRODUCT APPROVAL NUMBER NEXT TO |
| | EACH SPECIFIED CONNECTOR. |
| | RESPONSE: CLEARLY SPECIFY FLORIDA PRODUCT APPROVAL |
| | NUMBER FOR EACH CONNECTOR SPECIFIED ON THE WALL SECTION |
| | "A" , INCLUDING THE SIMPSON 5P2 . ALSO, THERE ARE OTHER |
| | CONNECTORS LIKE THE SIMPSON HTU28 THAT ARE NOT COVERED |
| | UNDER THE FLORIDA PRODUCT APPROVAL FL10865. REVISE AS |
| | REQUIRED. |
| | |
| | 3- ENGINEER OF RECORD TO APPROVE IN WRITING ALL PRODUCT |
| | APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY |
| | AMENDMENTS. |
| | RESPONSE: DOOR PRODUCT APPROVAL APPROVED BY THE |
| | ENGINEER DOESN'T MATCH PLANS. |
| | |
| | 4- THERE ARE TWO DIFFERENT SURVEYS SUBMITTED. PLANS AND |
| | SURVEY SUBMITTED DON'T MATCH. REVISE AS REQUIRED. |
| | PROVIDE CLEAR DRAWINGS SHOWN WHAT'S EXISTING AND WHAT'S |
| | PROPOSED. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | *** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | |