| 2015-08-29 06:19:28 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC 5TH EDITION RESIDENTIAL 301 |
| | |
| | 1. RATIONALE FOR EXPOSURE B NOT CLEAR. THE DEFAULT |
| | EXPOSURE IS C PER FBC AND ASCE7-10. THERE IS A LARGE |
| | OPEN AREA (APPROXIMATELY 400' WIDE X 1700' LONG) IN THE |
| | UPWIND DIRECTION, SOUTHEAST. IT APPEARS THAT THIS |
| | "PATCH CONDITION" WHICH IS IMMEDIATELY ADJACENT TO THIS |
| | STRUCTURE WOULD CREATE AN EXPOSURE C CONDITION. REVISE |
| | PLAN OR CLARIFY (USING ASCE7-10 OR FBC CODE OR |
| | COMMENTARY LANGUAGE, WITH CITATION NUMBERS). |
| | |
| | 2. PROPOSED DESIGN PRESSURES ARE +47.6 / -63.4. THIS |
| | DOES NOT STATE WHETHER THIS IS ASD OR ULTIMATE. |
| | ENGINEER MAY CONTACT ME TO DISCUSS THE IMPACT ON THIS |
| | (AND OTHER) JOBS, FBC 5TH EDITION RESIDENTIAL 301. |
| | PRESSURES MAY REMAIN "AS IS" BUT COMPLIANCE WITH THESE |
| | PRESSURES (AND INCREASED PRESSURES IF CHANGED TO |
| | EXPOSURE C) WOULD BE REQUIRED. UPON REQUEST, DESIGN |
| | PRESSURES PER THE TABLES IN FBC/ASCE7-10 CAN BE |
| | PROVIDED. |
| | |
| | 3. "REGULAR TAPCONS" ARE HIGHLIGHTED IN THE PRODUCT |
| | APPROVAL. CRETE FLEX PROPOSED ON THE INSTALLATION |
| | SCHEDULE. 12" / 8" IS HIGHLIGHTED, BUT 12" / 12" ANCHOR |
| | SPACING PRPOSED. |
| | |
| | 4. MOUNTING TYPE (PER INSTALLATION SCHEDULE) IS |
| | WINGNUT. THE NAMING CONVENTION ON THIS PRODUCT APPROVAL |
| | IS (FOR EXAMPLE) : 2 (TOP), 2(BOTTOM), 6(BOTTOM). THESE |
| | ARE THE ONES HIGHLIGHTED ON THE PRODUCT APPROVAL. THE |
| | ONES HIGHLIGHTED REQUIRED CONCRETE SUBSTRATE (FORMED |
| | AND POURED OR LINTEL). CBS STRUCTURES ARE TYPICALLY |
| | CONCRETE ON THE TOP, BLOCK ON THE BOTTOM. IT APPEARS |
| | THAT A DIFFERENT MOUTING TYPE (OR DIFFERENT FASTENER, |
| | OR BOTH) IS REQUIRED. |
| | |
| | 5. VALUE APPEARS LOW. PROVIDE |
| | RECEIPTS/INVOICES/MATERIAL COST EVIDENCE TO JUSTIFY THE |
| | VALUE OF $1000 FOR THREE NON IMPACT WINDOWS WITH |
| | ALUMINUM STORM PANELS. |
| | |
| | 6. SINGLE HUNG WINDOWS, SIZE 23, IN THE BEDROOMS ARE |
| | PROPOSED. REVISE THE PLAN TO INCLUDE THE FOLLOWING (PER |
| | FBC 5TH EDITION EXISTING BUILDING 704.1, RESIDENTIAL |
| | 310): |
| | |
| | STATE WHAT TYPE OF WINDOW IS THERE NOW IN THE BEDROOMS |
| | - AWNING, CASEMENT, SINGLE HUNG? |
| | |
| | STATE WHAT THE EXISTING CLEAR OPENING DIMENSIONS ARE. |
| | CLEAR OPENING IS THE OPENING WHICH EXISTS WHEN THE |
| | WINDOW IS FULLY OPEN. |
| | |
| | STATE WHAT THE PROPOSED CLEAR OPENING DIMENSIONS ARE. |
| | THIS CAN BE OBTAINED FROM THE MANUFACTURER. |
| | |
| | |