| 2015-09-14 16:05:50 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE |
| | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. |
| | 1. PG. E5: LARGE VIEW 4: DS-AC 12 & DS-AC 14 APPEARS TO |
| | BE ENCROACHING THE SAFE WORKING CLEARANCE REQUIRED BY |
| | NEC 110.26. |
| | 2. PG. E6: PER NEC 406.8, THE WP RECEPTACLE OUTDOORS ON |
| | THE ROOF SHALL ALSO BE LISTED AS WEATHER RESISTANT |
| | ?WR?. |
| | 3. PG. E7: VERIFY THE ALLOTTED CLEARANCE ABOUT |
| | ELECTRICAL EQUIPMENT SPECIFIED IN NEC 110.26. MAIN |
| | ELECTRICAL ROOM APPEARS TO BE IN VIOLATION. |
| | THE OVER CURRENT PROTECTION FOR THE FPL FEEDER IS 200 |
| | AMP. CORRECT ACCORDINGLY |
| | PROVIDE LOAD CALCS FOR PANEL ?L1? AND ?MSBD? TO |
| | ASCERTAIN PROPER ACCEPTANCE OF NEW LOADS. |
| | INDICATE CONDUCTOR SIZES FEEDING DISCONNECTS OFF OF |
| | PANEL L1 CIRCUITS 7 ? 10. |
| | DESCRIBE WHAT PART OF THE SCOPE INVOLVES PANEL ?F?. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU |
| | |