2015-10-02 09:24:42RESIDENTIAL (R3) ALTERATION/CHANGE OF OCCUPANCY,
 MECHANICAL REVIEW COMMENTS.
 CODE: FBC-5TH EDITION (2014).
  
 1- PROVIDE EQUIPMENT SIZING CALCULATIONS SHOWING
 COMPLIANCE WITH SEC. R403.6.1 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION.
  
 2- PROVIDE COMPLETE A/C PLANS SHOWING DUCTWORK SIZE,
 ALL SUPPLY AND RETURN GRILLS, CFM'S AND LISTING
 EQUIPMENT USED IN THE EQUIPMENT SIZING CALCULATIONS
 REQUIRED BY ITEM #1 ABOVE. SEC. 107.3.5.3(10) OF CITY
 AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDUITE THE REVIEW PROCESS.
 ***PLEASE REPLACE AND REMOVED ANY REVISED SHEET.
 SUBMITT OLD COPIES FOR REFERENCE.
  