| 2015-10-03 12:35:49 | 1ST REVIEW: FBC-R 2014 5TH ED. | | | | | | PLEASE SEE BUILDING PLAN REVIEW COMMENTS. APPARENTLY | | | WORK WAS DONE IN THE PAST TO CONVERT THE GROUND FLOOR | | | FROM GARAGE TO LIVING AREA. THIS PLAN DOES NOT ADDRESS | | | THE PREVIOUSLY NON PERMITTED WORK. PLEASE REVISE THE | | | PLAN TO SHOW AT A MINIMUM, THE FOLLOWING: | | | FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE | | | SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE | | | LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON | | | FLOOR PLAN. SHOW ALL DEVICE LOCATIONS. | | | | | | PLEASE FURTHER BE ADVISED OF THE FOLLOWING: | | | | | | ULTIMATELY,THE INSPECTOR MAY REQUIRE PREVIOUSLY | | | COMPLETED WORK TO BE MADE ACCESSIBLE AND OPEN FOR | | | INSPECTION OR REQUIRE ADDITIONAL DOCUMENTATION FOR ALL | | | CONCEALED WORK PREVIOUSLY COMPLETED PURSUANT TO FBC 110 | | | & FBC 117. | | | FBC 110.1 GENERAL. CONSTRUCTION OR WORK FOR WHICH A | | | PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY | | | THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK | | | SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION | | | PURPOSES UNTIL APPROVED. | | | FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR | | | TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE | | | TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN | | | APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY. | | | | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|