Plan Review Notes
Plan Review Notes For Permit 15080797
Permit Number 15080797
Review Stop E
Sequence Number 1
Notes
Date Text
2015-10-03 12:35:491ST REVIEW: FBC-R 2014 5TH ED.
  
 PLEASE SEE BUILDING PLAN REVIEW COMMENTS. APPARENTLY
 WORK WAS DONE IN THE PAST TO CONVERT THE GROUND FLOOR
 FROM GARAGE TO LIVING AREA. THIS PLAN DOES NOT ADDRESS
 THE PREVIOUSLY NON PERMITTED WORK. PLEASE REVISE THE
 PLAN TO SHOW AT A MINIMUM, THE FOLLOWING:
 FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE
 SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE
 LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN. SHOW ALL DEVICE LOCATIONS.
  
 PLEASE FURTHER BE ADVISED OF THE FOLLOWING:
  
 ULTIMATELY,THE INSPECTOR MAY REQUIRE PREVIOUSLY
 COMPLETED WORK TO BE MADE ACCESSIBLE AND OPEN FOR
 INSPECTION OR REQUIRE ADDITIONAL DOCUMENTATION FOR ALL
 CONCEALED WORK PREVIOUSLY COMPLETED PURSUANT TO FBC 110
 & FBC 117.
 FBC 110.1 GENERAL. CONSTRUCTION OR WORK FOR WHICH A
 PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY
 THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK
 SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION
 PURPOSES UNTIL APPROVED.
 FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR
 TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE
 TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN
 APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  