| 2015-11-04 17:04:32 | 2ND REVIEW: FBC 2014 MECHANICAL |
| | PERMIT #15080784 |
| | 11/4/2015 |
| | |
| | 1) SHEET 3.2M: THE O/A CALCULATIONS ARE INCORRECT. |
| | REFER TO TABLE 403.3: 7.5 CFM PER PERSON + .18 CFM PER |
| | SF. IS REQUIRED FOR THE DINING AREAS. PLEASE REVISE THE |
| | VENTILATION AND AIR BALANCE SCHEDULES ACCORDINGLY. |
| | 2) 3.2M: THE REVISED AC EQUIPMENT SCHEDULE INDICATES A |
| | NEW 5-TON AC SYSTEM: REFER TO SECTION C403.2.1 FBC-14 |
| | ENERGY CONSERVATION AND SUBMIT COOLING AND HEATING LOAD |
| | CALCULATIONS IN ACCORDANCE WITH THE ASHRAE STANDARD 183 |
| | OR ACCA MANUAL N. |
| | 3) REFER TO SECTION C101.4.3 FBC-14 ENERGY CONSERVATION |
| | AND PROVIDE ENERGY CALCULATIONS FOR THE PROPOSED |
| | RENOVATION. SEE SECTION C101.5 FOR COMPLIANCE SUBMITTAL |
| | INFORMATION. |
| | 4) SHEETS 1.3A & 3.2M: INDICATE HOW ACCESS FOR SERVICE |
| | WILL BE PROVIDED TO THE NEW AHU-1 ABOVE THE MEN'S ROOM |
| | CEILING. THIS APPEARS TO BE A HARD CEILING ALTHOUGH IT |
| | IS NOT LABELED ON THE RCP. IT IS ALSO NOT CLEAR HOW |
| | ACCESS WILL BE PROVIDED FOR AHU'S 2 & 3. PLEASE NOTE |
| | THAT CLEAR OPENINGS FOR ACCESS PANELS SHALL BE LARGE |
| | ENOUGH TO REMOVE EQUIPMENT WITHOUT REMOVING PERMANENT |
| | CONSTRUCTION- SECTION 306.1. |
| | 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE F/S |
| | DAMPER AT TTHE BOTTOM OF THE FIRE-RATED SHAFT WITH A |
| | REVIEW AND APPROVAL STAMP FROM THE ENGINEER OF RECORD. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |