| 2015-10-30 10:22:05 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | 1. SHEET 1.4A, INDICATES AN OCCUPANCY LOAD AND SEAT | | | LOAD OF 42 AT THE PATIO AREA. THE OCCUPNACY LOAD IS | | | MEASURED AT 30 AND SHALL NOT BE EXTENDED BY A SEAT | | | COUNT. | | | |
|