| Date |
Text |
| 2015-08-26 11:20:59 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | 1) SHEET 1.0A, DOOR SCHEDULE, THE DOOR SCHEDULE |
| | INDICATES DEADBOLTS ON THE EXIT DOOR. ALL EXIT DOOR |
| | HARDWARE SHALL COMPLY WITH NFPA 101, CHAPTER 7. |
| | |
| | DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM THE |
| | EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. LOCKS, |
| | IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY, TOOL, |
| | OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE |
| | EGRESS SIDE. |
| | |
| | PER SECTION 7.2.1.5.9, THE LOCK/LATCH RELEASING |
| | MECHANISM ON ALL DOORS SHALL OPEN THE DOOR WITH NOT |
| | MORE THAN ONE RELEASING OPERATION. THE RELEASING |
| | MECHANISM SHALL HAVE AN OBVIOUS METHOD OF OPERATION |
| | THAT IS READILY OPERATED UNDER ALL LIGHTING CONDITIONS. |
| | THE RELEASING DEVICE SHOULD BE CAPABLE OF BEING |
| | OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE TIGHT |
| | GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST TO |
| | OPERATE. |
| | |
| | A THUMB TURN LOCK IS NOT PERMITTED ON THE MAIN ENTRY |
| | DOOR(S). IN LIEU OF PANIC HARDWARE, THE MAIN ENTRY IS |
| | PERMITTED TO BE EQUIPPED WITH A KEYED LOCK WITH |
| | LOCK/UNLOCK INDICATOR WINDOW AND SIGNAGE STATING THE |
| | DOOR IS TO REMAIN UNLOCKED DURING BUSINESS HOURS. NO |
| | OTHER LOCKING OR LATCHING MECHANISMS ARE PERMITTED. |
| | |
| | THUMB-TURN LOCK TO BE EQUIPPED WITH AN ?OPEN/LOCKED? |
| | INDICATOR WINDOW (SUCH AS ADAMS RITE 4089 OR SIMILAR). |
| | |
| | FOR ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD OF 100 |
| | OR MORE PERSONS (50 PERSONS PER THE FLORIDA BUILDING |
| | CODE), PANIC HARDWARE SHALL BE PROVIDED ON DOORS TO |
| | RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR LATCHES ARE |
| | PERMITTED THAT WOULD NOT BE RELEASED BY THE PANIC |
| | HARDWARE. AS A SUBSTITUTE FOR PANIC HARDWARE, THE MAIN |
| | ENTRANCE IS PERMITTED TO HAVE AN INTERIOR KEYED DOOR |
| | LOCK (AND NO LATCH) WITH A READILY VISIBLE SIGN STATING |
| | THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING IS |
| | OCCUPIED. SIGN LETTERS SHALL BE AT LEAST 1 INCH IN |
| | HEIGHT. KEYED LOCK TO BE EQUIPPED WITH AN ?OPEN/LOCKED? |
| | INDICATOR WINDOW (SUCH AS ADAMS RITE 4089 OR SIMILAR). |
| | A THUMB TURN STYLE LOCK IS NOT PERMITTED TO BE |
| | SUBSTITUTED FOR A KEYED LOCK. |
| | |
| | 2) SHEET1.1A, ALL COOKING EQUIPMENT SHALL BE INSTALLED |
| | AND PROTECTED PER NFPA 96. |
| | |
| | 3) SHEET 1.3A & 1.4A, ADD AN EXIT SIGN LEADING TO THE |
| | REAR EXIT (AS HAND WRITTEN/DRAWN ON THE SHEETS) |
| | |
| | |
| | |