Text |
| 2015-10-06 13:30:04 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE ELECTRICAL REVIEW OF THE |
| | ABOVE MENTIONED JOB. BELOW ARE THE COMMENTS WITH |
| | REGARDS TO THE REQUIRED CORRECTIONS. THE PLANS SHALL BE |
| | REVISED TO ADDRESS FOLLOWING ITEMS; ONCE CORRECTED |
| | SHALL BE RESUBMITTED FOR ANOTHER REVIEW. |
| | |
| | 1. YOU INCORRECTLY REFERENCE THE 2010 NEC. THE |
| | APPLICABLE EDITION IS THE 2011 NEC; THERE NEVER WAS A |
| | 2010 EDITION. |
| | 2. YOU SHALL PROVIDE A DEDICATED SIGN OUTLET ABOVE |
| | EVERY PEDESTRIAN ENTRY, AS REQUIRED PER NEC 600.5 |
| | 3. YOU SHALL PROVIDE A DEDICATED SHOW WINDOW RECEPTACLE |
| | FOR EVERY 12 LINEAR FT. OR PORTION THEREOF OF SHOW |
| | WINDOW, PER NEC 210.62 |
| | 4. YOU SHALL INDICATE ON THE LIGHTING PLAN WHAT FIXTURE |
| | ARRANGEMENTS OR PROVISIONS HAVE BEEN MADE THE REQUIRED |
| | EMERGENCY LIGHTING. |
| | 5. YOU SHALL SUBMIT A LIGHT DENSITY CHART AND INDICATE |
| | COMPLIANCE WITH THE FBC-ENERGY CONSERVATION CODE |
| | SECTION C405. |
| | 6. THERE IS A MISSING EXIT LIGHT AS MARKED ON THE |
| | LIGHTING FLOOR PLAN. |
| | 7. THERE IS AN EXIT LIGHT THAT HAS TO BE RELOCATED |
| | ABOVE THE CORRESPONDING DOOR. |
| | 8. THE PANEL SCHEDULES DO NOT MATCH THE FLOOR PLAN |
| | CIRCUIT DESIGNATION. |
| | 9. INDICATE THE LOCATION OF ALL THE HVAC EQUIPMENT ON |
| | THE FLOOR PLAN. |
| | 10. IF THE ALARM CIRCUIT INDICATED ON PANEL A, 19 IS |
| | FOR A FIRE ALARM SYSTEM, ADDITIONAL REQUIREMENTS ARE |
| | NECESSARY. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU |
| | |