| 2015-08-25 16:52:48 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15080764 |
| | ADD: 400 N. FLAGLER 21 FLOOR COMMON AREA BETWEEN 2101 & |
| | 2102 |
| | CONT: MARYJULI CONSTRUCTION |
| | TEL: (561)386-6032 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE:TUES. AUGUST 25/2015 |
| | ACTION: DENIED |
| | |
| | 1) THE SOFFIT DOES NOT INDICATE THE CLEAR HEIGHT IS |
| | FROM THE BOTTOM OF THE SOFIT AND THE FLOOR. PLEASE |
| | PROVIDE CODE COMPLIANCE WITH 2014 FBC-B: |
| | 1003.2 MINIMUM CEILING HEIGHT. |
| | 1003.3.3.1 HEADROOM & PROTRUDING OBJECTS. |
| | |
| | 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |