| 2015-09-08 17:42:58 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE |
| | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. |
| | |
| | 1. INDICATE IF THE S/D INSIDE THE 1ST FLR. ELECTRIC |
| | ROOM NEW OR EXISTING? IT IS NOT MARKED AS EXISTING NOR |
| | INCLUDED ON THE RISER DIAGRAM. |
| | 2. INDICATE IF THE S/D INSIDE THE 1ST FLR. CORRIDOR, |
| | ADJACENT TO THE EVAC PANEL NEW OR EXISTING? IT IS NOT |
| | MARKED AS EXISTING NOR INCLUDED ON THE RISER DIAGRAM. |
| | 3. INDICATE IF THE D/D, RT & CM FOR RTU 4 ON THE ROOF |
| | ARE NEW OR EXISTING? THEY'RE NOT MARKED AS EXISTING NOR |
| | INCLUDED ON THE RISER DIAGRAM. |
| | 4. INDICATE IF THE D/D, RT & CM IN THE BALCONY ARE FOR |
| | RTU 3 AND IF THEY ARE NEW OR EXISTING? THEY'RE NOT |
| | MARKED AS EXISTING NOR INCLUDED ON THE RISER DIAGRAM. |
| | 5. IDENTIFY YOUR LINE WEIGHT/STYLE ON THE RISER DIAGRAM |
| | TO INDICATE THE NEW VS. THE EXISTING RUNS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |