| Plan Review Notes For Permit 15080670 |
| Permit Number |
15080670 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-09-14 06:52:51 | 1) SHT. A-1 REFERS TO THE 2010 FBC. TTHE CODE IN EFFECT | | | IS THE 2014 FBC. REVISE THE NOTE. | | | 2) SHT. A-2/P-1 - SANITARY RISER DIAGRAM - THE WASHING | | | MACHINES SHALL CONNECT TO A MINIMUM 3 INCH FIXTURE | | | BRANCH OR STACK. THE RISER DIAGRAM SHOWS THE WASHING | | | MACHINE DISCHARGING TO A 2 INCH FIXTURE BRANCH. 2014 | | | FBC-PLUMBING SEC. 406.2. | | | 3) SUBMIT MANUF. SPECIFICATIONS FOR THE TANKLESS WATER | | | HEATERS. WPB AMEND. TO FBC SEC. 107.2.1. | | | | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|