Plan Review Notes For Permit 15080670
Permit Number 15080670
Review Stop P
Sequence Number 1
Notes
Date Text
2015-09-14 06:52:511) SHT. A-1 REFERS TO THE 2010 FBC. TTHE CODE IN EFFECT
 IS THE 2014 FBC. REVISE THE NOTE.
 2) SHT. A-2/P-1 - SANITARY RISER DIAGRAM - THE WASHING
 MACHINES SHALL CONNECT TO A MINIMUM 3 INCH FIXTURE
 BRANCH OR STACK. THE RISER DIAGRAM SHOWS THE WASHING
 MACHINE DISCHARGING TO A 2 INCH FIXTURE BRANCH. 2014
 FBC-PLUMBING SEC. 406.2.
 3) SUBMIT MANUF. SPECIFICATIONS FOR THE TANKLESS WATER
 HEATERS. WPB AMEND. TO FBC SEC. 107.2.1.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR