Plan Review Notes
Plan Review Notes For Permit 15080670
Permit Number 15080670
Review Stop M
Sequence Number 1
Notes
Date Text
2015-09-11 08:43:211ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING
 PERMIT #15080670
 9/11/15
  
 1) REFER TO SECTION 809 FBC EXISTING BUILDING AND
 PROVIDE MECHANICAL PLANS, DETAILS, AND SPECIFICATIONS
 INCLUDING:
 A) MINIMUM VENTILATION CALCULATIONS FOR THE RENOVATED
 UNITS IN COMPLIANCE WITH TABLE 403.3 FBC-14 MECHANICAL.
 B) AC EQUIPMENT SCHEDULES.
 C) AC COOLING AND HEATING CALCULATIONS- SEE SECTION
 403.6.1 FBC-14 ENERGY CONSERVATION.
 D) ENERGY COMPLIANCE CALCULATIONS- SEE SECTION R101.4.3
 & TABLE R101.5.1 FBC-14 ENERGY CONSERVATION.
 E) AHRI CERTIFICATES.
 F) AC DUCT LAYOUT PLANS FOR EACH UNIT INDICATING THE
 TYPE AND SIZE OF DUCTS, SUPPLY CFM'S AT EACH DIFFUSER,
 MEANS OF RETURN AIR INCLUDING DIMENSIONS OF RETURN AIR
 GRILLS.
 G) AIR DISTRIBUTION SCHEDULE INDICATING THE TYPES AND
 SIZES OF DIFFUSERS AND GRILLS.
 H) CONDENSATE DISPOSAL PLANS- PRIMARY AND SECONDARY FOR
 EACH NEW AIR HANDLER- SEE SECTION 307 FBC-14
 MECHANICAL.
 I) WIND LOAD TIE DOWN ENGINEERING FOR MOUNTING THE AC
 CONDENSERS TO THE NEW PADS- SEE SECTION 301.15 FBC-14
 MECHANICAL.
 2) INDICATE ON THE PLANS HOW OUTSIDE AIR WILL BE
 PROVIDED TO EACH OF THE NEW AIR HANDLERS.- SEE SECTION
 R403.5.2 FBC ENERGY CONSERVATION.
 3) REFER TO SECTION 602 FBC-14 MECHANICAL AND SHOW
 COMPLIANCE FOR MATERIALS USED INSIDE THE AIR HANDLER
 CLOSETS INCLUDING THE TYPES OF CLOSET DOORS TO BE
 INSTALLED.
 4) REFER TO SECTION 603.1.1 AND PROVIDE A DIMENSIONED
 SECTION VIEW TO VERIFY ADEQUATE SPACE WILL BE PROVIDED
 IN THE AIR HANDLER CLOSETS.
 5) PROVIDE BATHROOM EXHAUST DETAILS: EXHAUST FAN
 EQUIPMENT SCHEDULES, EXHAUST DUCT RUNS AND TERMINATION
 LOCATIONS.
 6) PROVIDE DRYER EXHAUST AND MAKEUP AIR PLANS PER
 SECTION 504: SHOW THE TYPE AND SIZE OF EXHAUST DUCT,
 EXHAUST DUCT RUN AND TERMINATION LOCATION, AND INDICATE
 HOW MAKEUP AIR WILL BE SUPPLIED TO EACH DRYER.
 7) REFER TO SECTION 505 FBC-14 MECHANICAL AND PROVIDE
 KITCHEN EXHAUST VENTILATION PLANS.
 8) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE AC
 SYSTEMS AND THE DRYERS.
 PLEASE NOTE ADDITIONAL COMMENTS MAY FOLLOW SUBMITTAL OF
 REVISED PLANS AND RESPONSES TO ALL BUILDING DEPARTMENT
 COMMENTS.
  