Plan Review Notes
Plan Review Notes For Permit 15080670
Permit Number 15080670
Review Stop B
Sequence Number 1
Notes
Date Text
2015-09-09 14:40:53BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15080670
 ADD: 1408 FLORIDA AVE.
 CONT: SENTINEL DEVELOPMENT
 TEL: (561)373-4056
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. SEPT. 09/2015
 ACTION: DENIED
  
 1) PLEASE NOTE THE PALM BEACH COUNTY PROPERTY
 APPRAISERS OFFICE HAS THE IMPROVEMENT VALUE OF THIS
 PROPERTY VALUED AT $184,135.00. THE PERMIT APPLICATION
 INDICATES THE VALUE OF WORK TO BE COMPLETED UNDER THIS
 PERMIT A VALUE OF $170,000.00. THIS DOLLOR VALUE MEETS
 THE DEFINITION OF
 A RENOVATED BUILDING. RENOVATED BUILDING. A RESIDENTIAL
 OR NONRESIDENTIAL BUILDING UNDERGOING ALTERATION THAT
 VARIES OR CHANGES INSULATION, HVAC SYSTEMS, WATER
 HEATING SYSTEMS, OR EXTERIOR ENVELOPE CONDITIONS,
 PROVIDED THE ESTIMATED COST OF RENOVATION EXCEEDS 30
 PERCENT OF THE ASSESSED VALUE OF THE STRUCTURE.
  
 SHEET A1 THE INTERIOR -DEMO PLAN NOTES D-14 & D-15
 INDICATE THE REMOVAL OF THE AIR HANDLER IN THE ATTIC AS
 WELL AS THE DUCT WORK. SHEET A2 NOTE 18 INDICATES A NEW
 VERTICAL A/C HANDLIER AND NEW A/C CLOSET. NOTE THERE
 WAS A MECHANICAL EXACT CHANGE OUT PERMIT ISSUED
 15080568.
 NO DUCT WORK NO PLANS NO PLAN REVIEW.
  
 2014 ENERGY CODE. R101.4.7 BUILDING SYSTEMS AND
 COMPONENTS. THERMAL EFFICIENCY STANDARDS ARE SET FOR
 THE FOLLOWING BUILDING SYSTEMS AND COMPONENTS WHERE NEW
 PRODUCTS ARE INSTALLED OR REPLACED IN EXISTING
 BUILDINGS, AND FOR WHICH A PERMIT MUST BE OBTAINED. NEW
 PRODUCTS SHALL MEET THE MINIMUM EFFICIENCIES ALLOWED BY
 THIS CODE FOR THE FOLLOWING SYSTEMS AND COMPONENTS:
  
 HEATING, VENTILATING OR AIR CONDITIONING SYSTEMS.
 SERVICE WATER OR POOL HEATING SYSTEMS. LIGHTING
 SYSTEMS. REPLACEMENT FENESTRATION.
  
  
 2014 ENERGY CODE R101.5 COMPLIANCE. RESIDENTIAL
 BUILDINGS SHALL MEET THE RESIDENTIAL PROVISIONS OF THIS
 CODE.
  
 R101.5.1 COMPLIANCE MATERIALS. THE FLORIDA BUILDING
 COMMISSION SHALL APPROVE SPECIFIC COMPUTER SOFTWARE,
 WORKSHEETS, COMPLIANCE MANUALS AND OTHER SIMILAR
 MATERIALS THAT MEET THE INTENT OF THIS CODE. COMMISSION
 APPROVED CODE COMPLIANCE DEMONSTRATION FORMS CAN BE
 FOUND IN TABLE R101.5.1. PLEASE PROVIDE COMPLIANCE FOR
 THE ENERGY CODE BY EITHER PREFORMANCE BASED OR
 PRESCRIPTIVE BASED STANDARDS.
  
 2) THE PLANS INDICATE THEY WERE DESIGNED TO THE 2010
 FBC. PLEASE NOTE THE 2014 FBC- 5TH EDITION WAS ADOPTED
 STATEWIDE JUNE 30. 2015.
 NOTE THE PLANS WILL NEED TO BE REDESIGNED TO THE 2014
 FBC. PLEASE NOTE THE AMOUNT OF WORK INDICATED ON THE
 PLANS IS A LEVEL III ALTERATION .
  
 3) THE PLANS INDICATE THIS STRUCTURE TO BE A 3 UNIT R-2
 BUILDING WITH TENANT SEPARATION WALLS. PLEASE PROVIDE A
 SECTION THROUGH INDICATING CODE COMPLIANCE WITH FBC-B
 708.1(1) WALLS SEPARATING DWELLING UNITS.
  
 2014 FBC-B 420.2 SEPARATION WALLS. WALLS SEPARATING
 DWELLING UNITS IN THE SAME BUILDING, WALLS SEPARATING
 SLEEPING UNITS IN THE SAME BUILDING AND WALLS
 SEPARATING DWELLING OR SLEEPING UNITS FROM OTHER
 OCCUPANCIES CONTIGUOUS TO THEM IN THE SAME BUILDING
 SHALL BE CONSTRUCTED AS FIRE PARTITIONS IN ACCORDANCE
 WITH SECTION 708.
  
 2014 FBC-B 708.4 CONTINUITY. FIRE PARTITIONS SHALL
 EXTEND FROM THE TOP OF THE FOUNDATION OR FLOOR/CEILING
 ASSEMBLY BELOW TO THE UNDERSIDE OF THE FLOOR OR ROOF
 SHEATHING, SLAB OR DECK ABOVE OR TO THE
 FIRE-RESISTANCE-RATED FLOOR/CEILING OR ROOF/CEILING
 ASSEMBLY ABOVE, AND SHALL BE SECURELY ATTACHED THERETO.
 IN COMBUSTIBLE CONSTRUCTION WHERE THE FIRE PARTITIONS
 ARE NOT REQUIRED TO BE CONTINUOUS TO THE SHEATHING,
 DECK OR SLAB, THE SPACE BETWEEN THE CEILING AND THE
 SHEATHING, DECK OR SLAB ABOVE SHALL BE FIREBLOCKED OR
 DRAFTSTOPPED IN ACCORDANCE WITH SECTIONS 718.2 AND
 718.3 AT THE PARTITION LINE. PROVIDE THE FIRE RATED
 FIRE ASSEMBLY NUMBER UL GYPSUM ASSOCIATION ETC
  
 4) SHEET A2 DOES INDICATE THE WIND DESIGN CRITERIA, BUT
 THE PRESSURES ARE NOT PROVIDED FOR WINDOWS AND DOORS.
 PLEASE PROVIDE IN VASD TO COORESPOND TO THE PRESSURES
 IN THE PRODUCT APPROVALS. 2014 FBC-B 1603.1.4 WIND
 DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE: 5. DESIGN WIND PRESSURES TO BE USED FOR
 EXTERIOR COMPONENT AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL RESPONSIBLE FOR THE DESIGN OF THE
 STRUCTURE, PSF (KN/ M2).
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  