| Date |
Text |
| 2015-09-18 13:34:34 | ****CORRECTIONS**** |
| | COURTESY REVIEW - SCOPE CLARIFIED |
| | A DCA APPROVED MANUFACTURED BUILDING IS PROPOSED, WITH |
| | MODIFICATIONS |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | 1. BASED ON THE SITE PLAN PROVIDED, IT APPEARS THAT THE |
| | PROPOSED LOCATION FOR THIS SALES TRAILER IS 4847 FRED |
| | GLADSTONE DRIVE. SUBMIT A CHANGE OF ADDRESS THROUGH THE |
| | FRONT COUNTER OR REVISE THE SITE PLAN TO SHOW THE |
| | PROPOSED SALES TRAILER RELATIVE TO THE LOT LINES, FBC |
| | 107. |
| | |
| | 2. FS 553.80, PROVIDE THE STATE APPROVED PLANS AND |
| | STATE APPROVAL COVER SHEET WHICH SHOWS THE APPROVAL |
| | NUMBER. THIS SHOULD BE ON THE INSIGNIA. |
| | |
| | ADVISORY ONLY, PLANS PREPARED BY REBECCA M. GATES WERE |
| | NOT YET REVIEWED BY FIRE (FIRE HAD PLANS CHECKED OUT |
| | WHEN THESE SHEETS WERE SUBMITTED) BUT WILL BE REVIEWED |
| | WHEN PLANS ARE RESUBMITTED. |
| | |
| | PERMIT WILL BE ISSUED WITH PROVISO THAT, UPON BUILDING |
| | INSPECTION, THE DCA/DBPR INSIGNIA WILL BE REMOVED AND |
| | RETURNED TO DBPR. |
| | |
| | REVISE PLANS PREPARED BY REBECCA M. GATES TO INCLUDE |
| | GOVERNING CODE. |
| | |
| | IN ADDITION TO THE CHANGE IN FLOOR PLAN, IT APPEARS |
| | THAT A DOOR HAS BEEN ELIMINATED AND A WINDOW IS |
| | PROPOSED, BUT NO DETAIL WAS PROVIDED. PROVIDE A |
| | STRUCTURAL DETAIL AND INCLUDE WIND DESIGN CRITERIA FBC |
| | 1603.1.4. A PRODUCT APPROVAL REVIEWED BY DESIGNER OF |
| | RECORD REQUIRED. |
| | |
| | 3. PER ATCOUNCIL.ORG, THIS LOCATION IS RISK CATEGORY II |
| | 167 MPH. PLANS SUBMITTED ARE LIMITED TO 165 MPH, SEE |
| | SHEET C1, FBC 1609. PER THE STATE OF FLORIDA, IF AN |
| | EXISTING MANUFACTURED (MODULAR) BUILDING IS MOVVED TO A |
| | NEW LOCATION, THE RELOCATED BUILDING SHALL COMPLY WITH |
| | THE WIND SPEED OF THE NEW LOCATION. |
| | |
| | THE MANUFACTURED BUILDING PLANS AS SUBMITTED DO NOT |
| | COMPLY WITH THE WIND SPEED REQUIREMENT FOR THE |
| | LOCATION. PLEASE ADDRESS, EITHER BY PROVIDING A NEW |
| | MANUFACTURED BUILDING WHICH COMPLIES WITH 167MPH WIND |
| | SPEED, OR BY PROVIDING ENGINEERING TO INCREASE THE |
| | LIMITATION FOR THE BUILDING PROPOSED FROM 165MPH TO |
| | 167MPH. |
| | |
| | 4. SHOW 18 IN MANEUVERING CLEARANCE FOR DOORS, PULL |
| | SIDE, FBC ACCESSIBILITY 404.2.4.1, ROOMS 4 AND 5. |
| | |
| | 5. DETAIL 3 SK5, SEAT HEIGHT NOT CLEAR, FBC 5TH ED |
| | ACCESSIBILITY 604.4, PLEASE REVISE TO CLARIFY. DETAIL 2 |
| | SK5, PROVIDE LAV HEIGHT AND KNEE CLEARANCE, 606.3. |
| | |
| | 5. STAIR, RAMP, LANDING, RAILING DETAILS NOT PROVIDED, |
| | FBC CHAPTER 10, FBC ACCESSIBILITY. |
| | |
| | 6. SHEET SP1 SHOWS 38.8 FT FROM PROPOSED SALES OFFICE |
| | TO EXISTING RESNICK BUILDING. REVISE TO SHOW ASSUMED |
| | PROPERTY LINE BETWEEN THE TWO BUILDINGS, FBC 705.3 AND |
| | SHOW COMPLIANCE WITH FBC TABLES 602, 705.8. |
| | |
| | 7. FOR IMPACT FEES, EITHER: |
| | |
| | A. PROVIDE THE REMOVAL AGREEMENT WHEREIN OWNER AGREES |
| | THAT THE PROPOSED TEMPORARY SALES TRAILER WILL BE |
| | REMOVED BY A CERTAIN DATE (PER WILLIE SWOPE), OR |
| | |
| | B. AN IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS |
| | REQUIRED. 561-233-5025 FOR MORE INFORMATION; PROVIDE |
| | THE STAMPED PLAN AND RECEIPT SHOWING FEES WERE PAID, IF |
| | APPLICABLE. |
| | |
| | IF CONTRACTOR DOES NOT UNDERSTAND ITEM A, TAKE PLANS TO |
| | PALM BEACH COUNTY FOR IMPACT FEE ASSESSMENT. |
| | |
| | 8. IMPACT PROTECTION REQUIRED, SEE SITE INSTALLED |
| | ITEMS, FBC 1609.1.4. IF SHUTTERS ARE PROPOSED, PROVIDE |
| | THE PRODUCT APPROVAL AND COMPLETE THE SAMPLE |
| | INSTALLATION SCHEDULE: |
| | |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/SCHEDULE_FOR_INSTALLATION.PDF |
| | |
| | THIS CAN BE A PROVISO ITEM, SEPARATE PERMIT REQUIRED. |
| | |
| | 9. WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED |
| | SETS OF PLANS FOR PERMIT ISSUANCE. OLD SHEETS SHOULD BE |
| | MARKED "VOID" AND LEFT IN THE PERMIT APPLICATION |
| | PACKAGE. |
| | |
| | |
| | |