| 2015-09-12 14:26:35 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | 1. BASED ON THE SITE PLAN PROVIDED, IT APPEARS THAT THE |
| | PROPOSED LOCATION FOR THIS SALES TRAILER IS 4847 FRED |
| | GLADSTONE DRIVE. SUBMIT A CHANGE OF ADDRESS THROUGH THE |
| | FRONT COUNTER OR REVISE THE SITE PLAN TO SHOW THE |
| | PROPOSED SALES TRAILER RELATIVE TO THE LOT LINES, FBC |
| | 107. |
| | |
| | 2. SCOPE NOT CLEAR, FBC 107. |
| | |
| | COMPLETE PLANS WERE SUBMITTED FOR A "MODULAR |
| | STRUCTURE." PLEASE SEE FS 553.80, MODULAR STRUCTURES |
| | REQUIRE PLAN REVIEW AND APPROVAL BY THE STATE. IF THE |
| | MODULAR INSTALLATION IS PROPOSED, PROVIDE THE STATE |
| | APPROVED PLANS AND STATE APPROVAL COVER SHEET WHICH |
| | SHOWS THE APPROVAL NUMBER. THIS SHOULD BE ON THE |
| | INSIGNIA. |
| | |
| | SOMEONE ADDED PAGES AT SOME POINT IN THE REVIEW |
| | PROCESS. IF THESE PAGES WERE SUBMITTED AFTER OTHER |
| | REVIEWS WERE COMPLETE, RE-REVIEW BY THOSE TRADES IS |
| | REQUIRED. NO RESUBMITTAL FORM WAS PROVIDED. |
| | |
| | IF THE PLANS PREPARED BY REBECCA M. GATES ARE PROPOSED |
| | RATHER THAN THE PLAN WHICH APPEARS TO BE A DCA APPROVED |
| | MODULAR, PLEASE NOTE THE FOLLOWING PER STATE OF |
| | FLORIDA: |
| | |
| | CAN AN EXISTING MODULAR BUILDING BE MODIFIED OR |
| | RENOVATED? |
| | |
| | YES. ONSITE MODIFICATIONS TO EXISTING MODULAR BUILDINGS |
| | MUST BE PERMITTED AND INSPECTED BY THE JURISDICTION |
| | HAVING AUTHORITY (LOCAL BUILDING DEPARTMENT). ORIGINAL |
| | PLANS (OR ?AS-BUILT? PLANS) AND ANY MODIFICATIONS MUST |
| | BE PROVIDED TO THE LOCAL BUILDING DEPARTMENT. WHEN |
| | INSPECTED BY THE LOCAL BUILDING DEPARTMENT, THE |
| | DCA/DBPR INSIGNIA SHALL BE REMOVED AND RETURNED TO |
| | DBPR, AND A CERTIFICATE OF OCCUPANCY BE ISSUED IN LIEU |
| | OF THE DCA/DBPR INSIGNIA. RECERTIFICATION BY THE LOCAL |
| | JURISDICTION IS ONLY APPLICABLE FOR THAT JURISDICTION |
| | (NOT STATEWIDE). |
| | |
| | PLANS PREPARED BY REBECCA M. GATES SHOULD INCLUDE |
| | GOVERNING CODE. THE MODULAR PLANS ARE REQUIRED TO BE |
| | UPDATED TO CURRENT CODE. |
| | |
| | IN ADDITION TO THE CHANGE IN FLOOR PLAN, IT APPEARS |
| | THAT A DOOR HAS BEEN ELIMINATED AND A WINDOW IS |
| | PROPOSED, BUT NO DETAIL WAS PROVIDED. PROVIDE A |
| | STRUCTURAL DETAIL AND INCLUDE WIND DESIGN CRITERIA FBC |
| | 1603.1.4. A PRODUCT APPROVAL REVIEWED BY DESIGNER OF |
| | RECORD REQUIRED. |
| | |
| | A COMPLETE CHECKLIST CANNOT BE PROVIDED AS INTENT IS |
| | NOT ENTIRELY CLEAR. |
| | |
| | 3. PER ATCOUNCIL.ORG, THIS LOCATION IS RISK CATEGORY II |
| | 167 MPH. PLANS SUBMITTED ARE LIMITED TO 165 MPH, SEE |
| | SHEET C1, FBC 1609. PER THE STATE OF FLORIDA, IF AN |
| | EXISTING MANUFACTURED (MODULAR) BUILDING IS MOVVED TO A |
| | NEW LOCATION, THE RELOCATED BUILDING SHALL COMPLY WITH |
| | THE WIND SPEED OF THE NEW LOCATION. |
| | |
| | 4. SHOW 18 IN MANEUVERING CLEARANCE FOR DOORS, PULL |
| | SIDE, FBC ACCESSIBILITY 404.2.4.1, ROOMS 4 AND 5. |
| | |
| | 5. FOR THE NEW FLOOR PLAN, PROVIDE DETAILS WHICH SHOW |
| | COMPLIANCE WITH ALL REQUIREMENTS OF FBC 5TH EDITION |
| | ACCESSILIBITY. |
| | |
| | 5. STAIR, RAMP, LANDING, RAILING DETAILS NOT PROVIDED, |
| | FBC CHAPTER 10, FBC ACCESSIBILITY. |
| | |
| | 6. SHEET SP1 SHOWS 38.8 FT FROM PROPOSED SALES OFFICE |
| | TO EXISTING RESNICK BUILDING. REVISE TO SHOW ASSUMED |
| | PROPERTY LINE BETWEEN THE TWO BUILDINGS, FBC 705.3 AND |
| | SHOW COMPLIANCE WITH FBC TABLES 602, 705.8. |
| | |
| | 7. FOR IMPACT FEE PURPOSES, PROVIDE THE REMOVAL |
| | AGREEMENT WHEREIN OWNER AGREES THAT THE PROPOSED |
| | TEMPORARY SALES TRAILER WILL BE REMOVED BY A CERTAIN |
| | DATE (PER WILLIE SWOPE). IF THIS DOCUMENT CANNOT BE |
| | PROVIDED, AN IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY |
| | IS REQUIRED. 561-233-5025 FOR MORE INFORMATION. |
| | |
| | 8. IMPACT PROTECTION REQUIRED, SEE SITE INSTALLED |
| | ITEMS, FBC 1609.1.4. IF SHUTTERS ARE PROPOSED, PROVIDE |
| | THE PRODUCT APPROVAL AND COMPLETE THE SAMPLE |
| | INSTALLATION SCHEDULE: |
| | |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/SCHEDULE_FOR_INSTALLATION.PDF |
| | |
| | |