2015-10-14 11:02:19BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15080653
 ADD: 1819 OKEECHOBEE RD.
 CONT: GLOBAL CONSTRUCTION ASSOCIATES
 TEL: (954)971-1810
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W * 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. OCT. 14/2015
 ACTION: DENIED
  
 1) COVERSHEET ?T:
  
 1) COMPLIED.
  
 2) SHEET A1.1:
  
 2A) COMPLIED.
  
 2B) 2ND REQUEST. PLEASE PROVIDE A LIFE SAFETY PLAN FOR
 THIS TENANT, IN THE TRAINING ROOM WITH A OCCUPANT LOAD
 OF 72 REQUIRES (2) MEANS OF EGRESS.2014 FBC-B TABLE
 1015.1 BUSINESS OCCUPANCY MAXIMUM OCCUPANTS WITH ONE
 EXIT IS 49. THE RESPONSE THE 2ND MEANS OF EGRESS IS
 THROUGH THE SMALL PARTS ROOM 100, THROUGH A RATED WALL.
 THE SMALL PARTS ROOM # 100 IS A S2 OCCUPANCY, THIS IS
 THE REASON FOR THE FIRE RATING OF THE WALL PER TABLE
 508.4. 2014 FBC-B 1014.2 1014.2.1 EGRESS THROUGH
 INTERVENING SPACES. EXCEPTIION: MEANS OF EGRESS ARE NOT
 PROHIBITED THROUGH ADJOINING OR INTERVENING ROOMS OR
 SPACES IN A GROUP H, S OR F OCCUPANCY WHEN THE
 ADJOINING OR INTERVENING ROOMS OR SPACES ARE THE SAME
 OR A LESSER HAZARD OCCUPANCY GROUP. TABLE 508.4 DOES
 NOT REQUIRE OCCUPANCY SEPARATION BETWEEN B, F-1, M & S1
 OCCUPANCIES. THE PARTS ROOM IT APPEARS WOULD FALL INTO
 THE S-2 CATEGORY REQUIRING THE 1 HOUR SEPARATION WHEN
 FIRE SPRINKLERED.
  
  
 2C) COMPLIED.
  
 2D) SEMI-COMPLIED. DISCREPANCY IN PLANS SHEET A1.1
 VERSES A2.1. THE LIFE SAFETY PLANS SHOWS THERE IS NO
 LONGER A RATING BETWEEN ROOMS 103 & 104, WHERE AS A1.1
 STILL SHOWS A RATED WALL. THE MATERIAL LEGEND FOUND ON
 A1.1 UNDER THE HEAING EXISTING FIRE RATED WALLS :
 EXISTING FIRE RATED WALLS & REPAIR AS REQUIREDTO
 MAINTAIN FIRE RATING. 107.2.1.3. ADDITIONAL INFORMATION
 IS REQUIRED.
  
 COMMENT FROM 1ST REVIEW. THE EXISTING (1) HOUR FIRE
 RATED WALL BETWEEN WARE HOUSE 102 & 104 THE PLANS
 INDICATE A NEW 12?-0? WIDE OPENING IN NOTE # 5 FOUND ON
 THIS PLAN. THERE IS NO INFORMATION ON THIS OPENING IN
 THE DOOR SCHEDULE ON SHEET A3.1. NOTE SHEET A1.1 WALL
 LEGEND INDICATES THIS WALL TO BE A (1) HOUR FIRE RATED
 WALL.
  
 3) COMPLIED. WELDING CERTIFICATE FOR DAVID ORTIGOZA.
  
 4)SEMI-COMPLIED. NOA 15-0218.11 NOT REVIEWED BY THE
 DESIGNER OF RECORD, BEWARE OF ISSUE. SHEET SHEET 5 OF 5
 INDICATES THE RESTRAINT BRACKET FROM THE ROOF CURB TO
 ATTACH TO THE RTU. SHEET 2 OF 5, INDICATES THE USE OF
 (7) # 10 TEK SCREWS PER RETRAIN BRAKET.
 NOTE: WHERE THE NOA SHOWS THE # 10 TEK SCREWS THE
 RESTRAINT BRAKET DOES NOT ATTACH!!! IF THE TEK SCREWS
 ARE INSTALLED ON TOP OF THE CURB AS DEPICTED ON SHEET 5
 OF 5 THE VALUE FOR PULL OUT WILL BE LESS BECAUSE THEY
 ARE NO LONGER IN SHEER!!!! PLEASE EXAMINE CLOSELY.
  
 COMMENT FROM 1ST REVIEW. SHEET A3.2 DETAIL # A6 & M6.1
 BOTH SHOW NEW OR REPOSITIONED ROOF TOP CURBS BEING
 INSTALLED ON THE ROOF. PLEASE SUBMIT PRODUCT APPROVALS
 FOR THE NEW CURBS. 2014 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES/ ROOF TOP CURBS
  
 5) SECOND REQUEST. 2010 FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS.
  
 6) COMPLIED. 2014 FBC-B 1603.1.4 WIND DESIGN CRITERIA.
  
 7) SEMI -COMPLIED. NO PRODUCT APPROVALS WERE SUBMITTED
 FOR THE EXHAUST FAN NOR CURB. SHEET M6.1.THE PLANS WILL
 NEED TO SUPPLY THE CONNECTION OF THE RTU UNITS AND
 EXHAUST FANS TO THE ROOF TOP CURBING, TO RESIST THE
 EFFECTS OF UPLIFT, SLIDING AND OR OVERTURNING MOMENT.
 2014 FBC-B 1609.6.4.4.1 COMPONENTS & CLADDING
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  