| 2015-08-27 08:23:35 | 1ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING |
| | CODES |
| | PERMIT #15080653 |
| | 8/27/15 |
| | |
| | 1) COVER SHEET T: PLEASE UPDATE ALL 2010 CODE |
| | REFERENCES LISTED UNDER PROJECT DATA- THE 2014 FIFTH |
| | EDITION OF THE FLORIDA BUILDING CODES WENT INTO EFFECT |
| | ON JUNE 30, 2015. |
| | 2) REFER TO SECTION 809 FBC-14 EXISITING BUILDING CODE- |
| | TWO WAREHOUSE/OFFICE SUITES ARE NOW BEING COMBINED |
| | (SUITE NUMBERS NOT SHOWN ON PLANS) AND NEW ENLARGED |
| | CONDITIONED SPACES ARE BEING CONSTRUCTED. PLEASE |
| | PROVIDE THE FOLLOWING COMPLIANCE INFORMATION AS |
| | REQUIRED BY THE FLORIDA ENERGY CONSERVATION CODE: |
| | A) SUBMIT TWO SETS OF AC LOAD CALCULATIONS FOR THE NEW |
| | SPACES BEING CONDITIONED BY RTU'S 1, 1-1, 2, & 3. REFER |
| | TO SECTION C403.2.1 CALCULATION OF HEATING AND COOLING |
| | LOADS. |
| | DESIGN LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE |
| | PROCEDURES DESCRIBED IN THE ASHRAE/ACCA STANDARD 183 OR |
| | ACCA MANUAL N AND SHALL BE ATTACHED TO THE CODE |
| | COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT |
| | WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE |
| | MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE |
| | SIZING CALCULATION SHALL BE SUBMITTED WITH THE |
| | APPLICATION FOR THE MECHANICAL PERMIT. HEATING AND |
| | COOLING LOADS SHALL BE ADJUSTED TO ACCOUNT FOR LOAD |
| | REDUCTIONS THAT ARE ACHIEVED WHEN ENERGY RECOVERY |
| | SYSTEMS ARE UTILIZED IN THE HVAC SYSTEM IN ACCORDANCE |
| | WITH THE ASHRAEHVAC SYSTEMS AND EQUIPMENT HANDBOOK. |
| | ALTERNATIVELY, DESIGN LOADS SHALL BE DETERMINED BY AN |
| | APPROVED EQUIVALENT COMPUTATION PROCEDURE, USING THE |
| | DESIGN PARAMETERS SPECIFIED IN CHAPTER 3. |
| | B) SUBMIT TWO SETS OF ENERGY CALCULATIONS PER THE |
| | FOLLOWING CODE SECTIONS: C101.4.4 CHANGE IN OCCUPANCY |
| | OR USE. |
| | SPACES UNDERGOING A CHANGE IN OCCUPANCY THAT WOULD |
| | RESULT IN AN INCREASE IN DEMAND FOR EITHER FOSSIL FUEL |
| | OR ELECTRICAL ENERGY SHALL COMPLY WITH THIS CODE. WHERE |
| | THE USE IN A SPACE CHANGES FROM ONE USE IN TABLE |
| | C405.5.2(1) OR (2) TO ANOTHER USE IN TABLE C405.5.2(1) |
| | OR (2), THE INSTALLED LIGHTING WATTAGE SHALL COMPLY |
| | WITH SECTION C405.5. |
| | C101.4.5 CHANGE IN SPACE CONDITIONING. |
| | ANY NONCONDITIONED SPACE THAT IS ALTERED TO BECOME |
| | CONDITIONED SPACE SHALL BE REQUIRED TO BE BROUGHT INTO |
| | FULL COMPLIANCE WITH THIS CODE. |
| | 3) SHEET M6.1: PLEASE CLARIFY THE SEQUENCE OF OPERATION |
| | RELATING TO FAN SHUT DOWN OF THE AC SYSTEMS. WILL THE |
| | SYSTEMS ALLL BE LINKED TOGETHER? |
| | 4) SHEETS A6 & M7.1: PROVIDE THE WIND LOAD DESIGN |
| | CRITERIA FOR INSTALLATION OF THE RTU'S, RTU CURBS, AND |
| | EF-1-1. REVIEW SECTIONS 301.5 FBC-14 MECHANICAL, AND |
| | SECTION 1609 FBC-14 BUILDING. PROVIDE DESIGN PRESSURES |
| | ON THE PLAN -LATERAL AND UPLIFT- AND COMPLETE |
| | INSTALLATION DETAILS. |
| | 5) SHUTOFF DAMPER CONTROLS FOR ALL RTU- O/A SUPPLIES IS |
| | REQUIRED IN ACCORDANCE WITH C403.2.4.4. VERIFY |
| | COMPLIANCE FOR ALL UNITS. |
| | |