| 2015-09-01 07:23:55 | |
| | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15080653 |
| | ADD: 1819 OKEECHOBEE RD. |
| | CONT: GLOBAL CONSTRUCTION ASSOCIATES |
| | TEL: (954)971-1810 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W * 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. SEPT. 01/2015 |
| | ACTION: DENIED |
| | |
| | 1) COVERSHEET ?T: |
| | |
| | 1A) INDICATES THE PLANS WERE DESIGNED TO THE 2010 FBC, |
| | PLEASE NOTE THE 2014, 5TH EDITION WAS ADOPTED STATEWIDE |
| | JUNE 30/ 2015. PLEASE UPDATE PLANS. |
| | |
| | 1B) THE CONSTRUCTION TYPE IS LISTED AS A BLDG TYPE IV |
| | THE ORIGINAL BUILDING WAS BUILT UNDER THE 2001 FBC-B. |
| | THAT CODE AND BUILDING TYPE IS THE EQUAL TO UNDER THE |
| | 2014 FBC-B IIB. PLEASE UPDATE PLANS. |
| | |
| | 2) SHEET A1.1: |
| | |
| | 2A) THE TRAINING ROOM IS APPROXIMATELY 1430 SQ. FT./ 20 |
| | SQ. FT. NET= 72 OCCUPANT LOAD. SEE THE 2014 FBC-B TABLE |
| | 1014.1.2. |
| | |
| | 2B) PLEASE PROVIDE A LIFE SAFETY PLAN FOR THIS TENANT, |
| | IN THE TRAINING ROOM WITH A OCCUPANT LOAD OF 72 |
| | REQUIRES (2) MEANS OF EGRESS. |
| | 2014 FBC-B TABLE 1015.1 BUSINESS OCCUPANCY MAXIMUM |
| | OCCUPANTS WITH ONE EXIT IS 49. |
| | 2014 FBC-B TABLE 1016.2 EXIT ACCESS TRAVEL |
| | |
| | 2C) THE EXISTING (1) HOUR FIRE RATED WALL BETWEEN WARE |
| | HOUSES 103 & 104 INDICATES IN THE WALL LEGEND A (1) |
| | HOUR FIRE RATED WALL TO REMAIN. IN THIS WALL THERE IS A |
| | DOOR IDENTIFIED AS ER1, THE DOOR SCHEDULE FOUND ON |
| | SHEET A3.1 INDICATES IN THE DOOR NOTES THIS DOOR IS TO |
| | BE RELOCATED. WHAT IS GOING TO HAPPEN IN THIS OPENING |
| | IN THE RATED WALL, IS IT TO BE CLOSED UP? 2014 FBC-B |
| | 716.5/ TABLE 716.5 FIRE DOOR AND SHUTTER ASSEMBLIES. |
| | |
| | 2D) THE EXISTING (1) HOUR FIRE RATED WALL BETWEEN WARE |
| | HOUSE 102 & 104 THE PLANS INDICATE A NEW 12?-0? WIDE |
| | OPENING IN NOTE # 5 FOUND ON THIS PLAN. THERE IS NO |
| | INFORMATION ON THIS OPENING IN THE DOOR SCHEDULE ON |
| | SHEET A3.1. NOTE SHEET A1.1 WALL LEGEND INDICATES THIS |
| | WALL TO BE A (1) HOUR FIRE RATED WALL. |
| | |
| | 3) SHEET A3.2 DETAIL # A6 INDICATES IN ROOF TOP A/C |
| | CURB INSTALLATIONS? WITH NEW STEEL FRAMING MEMBERS |
| | BEING WELDED INTO PLACE. PLEASE NOTE THE FRAMING AND |
| | WELDED CONNECTIONS WILL REQUIRE A 3RD PARTY TO CERTIFY |
| | WORK COMPLETED IN THIS AREA OR A RESIDENT INSPECTOR |
| | ONSITE WITH PAPERWORK FILED WITH CITY BEFORE PERMIT |
| | ISSUANCE, PLEASE INDICATE IN WRITING YOUR CHOICE. |
| | RESIDENT INSPECTOR FORMS MUST BE FILED OUT AND RETURNED |
| | FOR REVIEW. |
| | 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 110.3.9. |
| | SUCH INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES |
| | WORK IS UNDERWAY ON THE STRUCTURAL ELEMENTS OF THE |
| | BUILDING. SUCH INSPECTORS SHALL BE A REGISTERED |
| | ARCHITECT, OR ENGINEER, OR A PERSON LICENSED UNDER |
| | CHAPTER 468, PART XII, FLORIDA STATUTES. SUCH |
| | INSPECTORS SHALL SUBMIT WEEKLY PROGRESS REPORTS |
| | INCLUDING THE DAILY INSPECTIONS TO THE BUILDING |
| | OFFICIAL, AND INCLUDING A CODE COMPLIANCE OPINION OF |
| | THE RESIDENT INSPECTOR. |
| | |
| | 3A) 110.4 INSPECTION AGENCIES. THE BUILDING OFFICIAL IS |
| | AUTHORIZED TO ACCEPT REPORTS OF APPROVED INSPECTION |
| | AGENCIES, PROVIDED SUCH AGENCIES SATISFY THE |
| | REQUIREMENTS AS TO QUALIFICATIONS AND RELIABILITY. |
| | |
| | 3B) 110.5 INSPECTION REQUESTS. IT SHALL BE THE DUTY OF |
| | THE HOLDER OF THE BUILDING PERMIT OR THEIR DULY |
| | AUTHORIZED AGENT TO NOTIFY THE BUILDING OFFICIAL WHEN |
| | WORK IS READY FOR INSPECTION. IT SHALL BE THE DUTY OF |
| | THE PERMIT HOLDER TO PROVIDE ACCESS TO AND MEANS FOR |
| | INSPECTIONS OF SUCH WORK THAT ARE REQUIRED |
| | BY THIS CODE. |
| | |
| | 3C) 110.6 APPROVAL REQUIRED. WORK SHALL NOT BE DONE |
| | BEYOND THE POINT INDICATED IN EACH SUCCESSIVE |
| | INSPECTION WITHOUT FIRST OBTAINING THE APPROVAL OF THE |
| | BUILDING INSPECTOR. THE BUILDING OFFICIAL, UPON |
| | NOTIFICATION, SHALL MAKE THE REQUESTED INSPECTIONS AND |
| | SHALL EITHER INDICATE THE PORTION OF THE CONSTRUCTION |
| | THAT IS SATISFACTORY AS COMPLETED, OR NOTIFY THE PERMIT |
| | HOLDER OR HIS OR HER AGENT WHEREIN THE SAME FAILS TO |
| | COMPLY WITH THIS CODE. ANY PORTIONS THAT DO NOT COMPLY |
| | SHALL BE CORRECTED AND SUCH PORTION SHALL NOT BE |
| | COVERED OR CONCEALED UNTIL AUTHORIZED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 4) SHEET A3.2 DETAIL # A6 & M6.1 BOTH SHOW NEW OR |
| | REPOSITIONED ROOF TOP CURBS BEING INSTALLED ON THE |
| | ROOF. PLEASE SUBMIT PRODUCT APPROVALS FOR THE NEW |
| | CURBS. 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(D) ROOFING PRODUCTS AND ASSEMBLIES/ ROOF TOP CURBS |
| | |
| | 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS. |
| | |
| | 6) THE PLANS DO NOT PROVIDE THE WIND DESIGN CRITERIA |
| | FOR THE ROOF TOP CURBS. 2014 FBC-B 1603.1.4 WIND DESIGN |
| | DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 6.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| | VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 1609.3.1. |
| | |
| | 6.2. RISK CATEGORY. |
| | |
| | 6.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. |
| | |
| | 6.. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 6.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/ |
| | M2). |
| | |
| | 7) THE PLANS WILL NEED TO SUPPLY THE CONNECTION OF THE |
| | RTU UNITS AND EXHAUST FANS TO THE ROOF TOP CURBING, TO |
| | RESIST THE EFFECTS OF UPLIFT, SLIDING AND OR |
| | OVERTURNING MOMENT. 2014 FBC-B 1609.6.4.4.1 COMPONENTS |
| | & CLADDING |
| | |
| | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |