Plan Review Notes
Plan Review Notes For Permit 15080635
Permit Number 15080635
Review Stop P
Sequence Number 2
Notes
Date Text
2015-10-08 11:47:121) SUBMIT TWO COPIES OF A PLUMBING PLAN, WATER RISER,
 AND SANITARY RISER THAT REFLECTS THE ENTIRE SCOPE OF
 PLUMBING WORK TO BE DONE. WPB AMEND. TO FBC SEC. 107.1.
 THERE WAS NO PLUMBING PLAN IN THE RESUBMITTED SET OF
 PLANS.
 2) SINCE THIS IS A CHANGE OF OCCUPANCY, A MINIMUM OF 2
 DRINKING FOUNTAINS SHALL BE PROVIDED PER THE 2014 FBC-
 ACCESSIBILITY SEC. 211.2.
 3) THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE, NOT TO CENTER AS SHOWN PER THE FBC
 -ACCESS. SEC.609.4.
 4) THE SHOWER CONTROLS SHALL BE LOCATED ON THE SIDE
 WALL OPPOSITE THE SEAT AND SHALL BE LOCATED ON THE
 CONTROL WALL 15 INCHES MAXIMUM FROM THE CENTERLINE OF
 THE SEAT TOWARD THE SHOWER OPENING PER THE 2014
 FBC-ACCESS. SEC.608.5.1. CLEARLY SHOW THIS ON THE
 PLANS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  