| Plan Review Notes For Permit 15080635 |
| Permit Number |
15080635 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-10-08 11:47:12 | 1) SUBMIT TWO COPIES OF A PLUMBING PLAN, WATER RISER, | | | AND SANITARY RISER THAT REFLECTS THE ENTIRE SCOPE OF | | | PLUMBING WORK TO BE DONE. WPB AMEND. TO FBC SEC. 107.1. | | | THERE WAS NO PLUMBING PLAN IN THE RESUBMITTED SET OF | | | PLANS. | | | 2) SINCE THIS IS A CHANGE OF OCCUPANCY, A MINIMUM OF 2 | | | DRINKING FOUNTAINS SHALL BE PROVIDED PER THE 2014 FBC- | | | ACCESSIBILITY SEC. 211.2. | | | 3) THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE | | | GRIPPING SURFACE, NOT TO CENTER AS SHOWN PER THE FBC | | | -ACCESS. SEC.609.4. | | | 4) THE SHOWER CONTROLS SHALL BE LOCATED ON THE SIDE | | | WALL OPPOSITE THE SEAT AND SHALL BE LOCATED ON THE | | | CONTROL WALL 15 INCHES MAXIMUM FROM THE CENTERLINE OF | | | THE SEAT TOWARD THE SHOWER OPENING PER THE 2014 | | | FBC-ACCESS. SEC.608.5.1. CLEARLY SHOW THIS ON THE | | | PLANS. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|