| Date |
Text |
| 2015-10-14 16:08:05 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE |
| | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. |
| | 1. THE DRAWINGS AS SUBMITTED ARE MISSING SEVERAL EXIT |
| | LIGHTS AS MENTIONED BELOW: ROOM 102, 103, 105, AT THE |
| | SOUTH END OF THE WEST CORRIDOR, AT THE EGRESS DOOR OF |
| | STAIR 203 |
| | 2. THERE ARE MISSING EMERGENCY LIGHTS AS INDICATED |
| | BELOW: AN EXIT/EMERGENCY COMBO AT THE BOTTOM OF STAIR |
| | 111, ROOM 200 |
| | 3. NEC 314.27 HAS SPECIFIC WEIGHT REQUIREMENTS FOR |
| | CEILING OUTLET AND FOR CEILING FAN OUTLETS. |
| | 4. NEC 600.5 REQUIRES THAT THERE BE A DEDICATED OUTLET |
| | AT EVERY PEDESTRIAN DOOR TO EVERY COMMERCIAL |
| | ESTABLISHMENT FOR SIGN PURPOSES. |
| | 5. NEC 422.52 REQUIRES THAT THE CIRCUIT FOR THE EWC |
| | (DRINKING FOUNTAIN) BE GFCI PROTECTED. |
| | 6. ALL FIRE ALARM WORK SHALL BE PERFORMED UNDER A |
| | SEPARATE AND STAND ALONE PERMIT. |
| | WHEN RESUBMITTING, YOU SHALL PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH COMMENT ITEM ALONG WITH THE |
| | CITY?S RE-SUBMITTAL FORM. SEE LINK BELOW: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | ADDITIONALLY, IT IS REQUIRED THAT YOU INSERT THE |
| | CORRECTED PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID |
| | THE PREVIOUSLY REVIEWED SHEETS AND LEAVE IN FOR |
| | COMPARATIVE REVIEW. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |