Plan Review Notes
Plan Review Notes For Permit 15080635
Permit Number 15080635
Review Stop M
Sequence Number 1
Notes
Date Text
2015-08-28 12:44:371ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15080635
 8/28/15
  
 1) SHEET A1 CODE DATA: PROVIDE THE CLASSIFICATION OF
 THE PROPOSED WORK IN ACCORDANCE WITH THE FLORIDA
 EXISTING BUILDING CODE FIFTH EDITION 2014. REFER TO
 CHAPTER 5 AND INDICATE LEVEL 1, 2, 3, OR CHANGE OF
 OCCUPANCY ON THE PLANS.
 2) REFER TO SECTION C101.4.4 FBC-14 ENERGY
 CONSERVATION: CHANGE IN OCCUPANCY OR USE.
 SPACES UNDERGOING A CHANGE IN OCCUPANCY THAT WOULD
 RESULT IN AN INCREASE IN DEMAND FOR EITHER FOSSIL FUEL
 OR ELECTRICAL ENERGY SHALL COMPLY WITH THIS CODE. WHERE
 THE USE IN A SPACE CHANGES FROM ONE USE IN TABLE
 C405.5.2(1) OR (2) TO ANOTHER USE IN TABLE C405.5.2(1)
 OR (2), THE INSTALLED LIGHTING WATTAGE SHALL COMPLY
 WITH SECTION C405.5.
 PLEASE PROVIDE ENERGY CALCULATIONS USING COMPLIANCE
 MATERIALS SPECIFIED IN SECTION C101.5.1.
 3) REFER TO SECTION 809.1 FBC-14 EXISTING BUILDING AND
 PROVIDE AC LOAD CALCULATIONS FOR THE AC SYSTEMS.
 C403.2.1 FBC-14 CALCULATION OF HEATING AND COOLING
 LOADS.
 DESIGN LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE
 PROCEDURES DESCRIBED IN THE ASHRAE/ACCA STANDARD 183 OR
 ACCA MANUAL N AND SHALL BE ATTACHED TO THE CODE
 COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT
 WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE
 MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE
 SIZING CALCULATION SHALL BE SUBMITTED WITH THE
 APPLICATION FOR THE MECHANICAL PERMIT. HEATING AND
 COOLING LOADS SHALL BE ADJUSTED TO ACCOUNT FOR LOAD
 REDUCTIONS THAT ARE ACHIEVED WHEN ENERGY RECOVERY
 SYSTEMS ARE UTILIZED IN THE HVAC SYSTEM IN ACCORDANCE
 WITH THE ASHRAEHVAC SYSTEMS AND EQUIPMENT HANDBOOK.
 ALTERNATIVELY, DESIGN LOADS SHALL BE DETERMINED BY AN
 APPROVED EQUIVALENT COMPUTATION PROCEDURE, USING THE
 DESIGN PARAMETERS SPECIFIED IN CHAPTER 3.
 4) M1: INDICATE HOW ACCESS TO AHU-1 & AHU-2 IS BEING
 PROVIDED. REFER TO THE FOLLOWING CODE SECTIONS AND
 PROVIDE DRAWINGS AND DETAILS VERIFYING COMPLIANCE:
 SECTION 306.1, AND 603.1.1 FBC-14 MECHANICAL.
 5) M1: DUCT SMOKE DETECTORS SHALL BE LOCATED IN THE
 RETURN AIR SYSTEMS OF AHU-1 AND AHU-2 IN COMPLIANCE
 WITH SECTIONS 606.2.1 AND 606.2.2 FBC-14 MECHANICAL.
 PROVIDE A NARRATIVE AND DIAGRAM DESCRIBING CONTROLS
 OPERATION AND SUPERVISION OF THE DETECTORS PER SECTIONS
 606.4 & 606.4.1.
 6) M1: PROVIDE A MEANS OF RETURN AIR FROM THE
 STRETCHING ROOM AND HALLWAY TO AHU-2. SEE SECTION 601.5
 MECHANICAL.
 7) M1: PLEASE CLARIFY WHY AIR FROM THE AHU-1 SUPPLY IN
 THE SYNERGY ROOM IS BEING RETURNED TO AHU-2. SEE
 SECTION 601.5.
 8) M2: PROVIDE SUPPORT AND HANGER DETAILS FOR THE
 FIBROUS DUCTS, THE VAV BOXES, AND THE EXHAUST FANS.
 9) M1 & M2: PROVIDE CONDENSATE DISPOSAL PLANS FOR AHU-1
 & 2, AND THE RTU : SEE SECTION 307.2- 307.2.3 FBC-14
 MECHANICAL.
 10) THE EXHAUST FAN IN THE TOILET/SHOWER ROOM 112 SHALL
 BE MINIMUM 100 CFM PER TABLE 403.3
 11) PROVIDE STRUCTURAL DETAILS, AND THE WIND DESIGN
 CRITERIA AND PRESSURES FOR INSTALLATION OF THE NEW RTU
 ROOF OPENING, THE RTU CURB, AND MOUNTING OF THE RTU-
 REFER TO SECTION 301.15 FBC-14 MECHANICAL.
 12) PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE TRANE
 RTU/O/A UNITS, AND THE VAV BOXES.
 13) PROVIDE A FLORIDA PRODUCT APPROVAL OR MIAMI-DADE
 NOA FOR THE EXTERIOR WALL LOUVER- FL. DEPT. OF
 COMMUNITY AFFAIRS RULE 9N-3.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  