Plan Review Notes
Plan Review Notes For Permit 15080635
Permit Number 15080635
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-08-20 14:36:59THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET A1, THERE IS A NOTE INDICATING STEEL STAIR NOT
 AN EXIT, YET ON SHEET E1, THERE IS AND EXIT SIGN AT THE
 STAIR. PLEASE CLARIFY.
  
 2) SHEET A1 , DOUBLE DOORS 102A AND 103A INDICATE THEY
 OPEN INTO THE EXIT CORRIDOR, SHEET E1 SHOW SOME TYPE OF
 EQUIPMENT AND OTHER DOORS OPENING ALONG THE CORRIDOR
 WALL.
 PER NFPA 101 CHAPTER 7, MEANS OF EGRESS
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY
 OPEN.
  
 PLEASE PROVIDE ACCURATE DIMENSIONS ALONG THE CORRIDOR
 MEETING THE ABOVE REQUIREMENTS.
  
 3) SHEET A6, ON THE DOOR SCHEDULE IT INDICATES DOOR
 STOPS ON DOORS 102A AND 103A, BASED ON THE ABOVE DOOR
 STOPS SHALL NOT BE INSTALLED ON THESE DOORS. THEY SHALL
 ALSO OPEN FULLY TO WITHIN THE 7IN. NOTED ABOVE.
  
 4) SHEET A1, INDICATES AREA 203 AS EXISTING STAIR AND
 APPEARS TO BE THE REQUIRED EXIT FROM THE MEZZANINE. NO
 DETAIL IS PROVIDED FOR THIS EXIT STAIR AND NO EXIT
 DISCHARGE IS INDOCATED. PLEASE CLARIFY.
  
 5) SHEET A1, PROVIDE NOTE INDICATING THE PROPOSED
 PROJECT SHALL MEET THE REQUIREMENTS OF THE 5TH EDITION
 OF FLORIDA FIRE PREVENTION CODE INCLUDING THE 2012
 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER APPLICABLE
 CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 6) COMPLETE LIFE SAFETY PLANS SHALL BE PROVIDED THAT
 ILLUSTRATE OCCUPANT LOADS, TRAVEL DISTANCES, COMMON
 PATHS OF TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS,
 EMERGENCY LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE
 EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES
 AND EQUIPMENT.