| 2015-08-20 14:36:59 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) SHEET A1, THERE IS A NOTE INDICATING STEEL STAIR NOT |
| | AN EXIT, YET ON SHEET E1, THERE IS AND EXIT SIGN AT THE |
| | STAIR. PLEASE CLARIFY. |
| | |
| | 2) SHEET A1 , DOUBLE DOORS 102A AND 103A INDICATE THEY |
| | OPEN INTO THE EXIT CORRIDOR, SHEET E1 SHOW SOME TYPE OF |
| | EQUIPMENT AND OTHER DOORS OPENING ALONG THE CORRIDOR |
| | WALL. |
| | PER NFPA 101 CHAPTER 7, MEANS OF EGRESS |
| | 7.2.1.4.3 DOOR LEAF ENCROACHMENT |
| | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS |
| | OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE |
| | REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY, |
| | OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT |
| | MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A |
| | CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN, |
| | UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET: |
| | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN |
| | EXISTING BUILDING. |
| | (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS |
| | PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED |
| | WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY |
| | OPEN. |
| | |
| | PLEASE PROVIDE ACCURATE DIMENSIONS ALONG THE CORRIDOR |
| | MEETING THE ABOVE REQUIREMENTS. |
| | |
| | 3) SHEET A6, ON THE DOOR SCHEDULE IT INDICATES DOOR |
| | STOPS ON DOORS 102A AND 103A, BASED ON THE ABOVE DOOR |
| | STOPS SHALL NOT BE INSTALLED ON THESE DOORS. THEY SHALL |
| | ALSO OPEN FULLY TO WITHIN THE 7IN. NOTED ABOVE. |
| | |
| | 4) SHEET A1, INDICATES AREA 203 AS EXISTING STAIR AND |
| | APPEARS TO BE THE REQUIRED EXIT FROM THE MEZZANINE. NO |
| | DETAIL IS PROVIDED FOR THIS EXIT STAIR AND NO EXIT |
| | DISCHARGE IS INDOCATED. PLEASE CLARIFY. |
| | |
| | 5) SHEET A1, PROVIDE NOTE INDICATING THE PROPOSED |
| | PROJECT SHALL MEET THE REQUIREMENTS OF THE 5TH EDITION |
| | OF FLORIDA FIRE PREVENTION CODE INCLUDING THE 2012 |
| | EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER APPLICABLE |
| | CODES OR STANDARDS. |
| | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 13, 2010 EDITION. |
| | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 72, 2010 EDITION. |
| | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 241, 2009 EDITION. |
| | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 10, 2010 EDITION. |
| | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. |
| | |
| | 6) COMPLETE LIFE SAFETY PLANS SHALL BE PROVIDED THAT |
| | ILLUSTRATE OCCUPANT LOADS, TRAVEL DISTANCES, COMMON |
| | PATHS OF TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS, |
| | EMERGENCY LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE |
| | EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES |
| | AND EQUIPMENT. |