| | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15080635 |
| | ADD: 312 CLEMATIS ST. / 1ST FLOOR |
| | CONT: COMPLETE HOME IMPROVEMENT |
| | TEL: (954)636-2238 |
| | E-MAIL: ????????????????????? |
| | |
| | 2014 FLORIDA BUILDING CODE W |
| | * 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. SEPT. 01/ 2015 |
| | ACTION: DENIED |
| | |
| | BUILDING BUILT IN 1919 |
| | |
| | 1) SHEET A1: |
| | |
| | 1A) 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.3.5.1.1 |
| | MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL BUILDINGS. |
| | MINIMUMTYPE OF CONSTRUCTION SHALL BE DETERNINED FBC-B |
| | TABLE 503. 3 STORIES + MEZANINE |
| | |
| | SPRINKLERED OR NOT, AREA OR HEIGHT INCREASE TAKEN? |
| | |
| | LIFE SAFETY PLANS TO INCLUDE; |
| | OCCUPANCY LOAD |
| | GROSS |
| | NET |
| | MEANS OF EGRESS |
| | EXIT ACCESS |
| | EXIT |
| | EXIT PASSAGEWAY |
| | EXIT DISCHARGE |
| | STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION |
| | DOORS RATED |
| | EMERGENCY LIGHTING AND EXIT SIGNS |
| | CONSTRUCTION REQUIREMENTS FIRE RATED EXIT ENCLOSURES |
| | |
| | FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL INCLUDE |
| | THE FOLLOWING COMPONENTS: |
| | FIRE-RESISTANT SEPARATIONS EXTERIOR WALLS TABLE 601 & |
| | 602 |
| | |
| | 1B) 2014 FBC-EXISITNG BUILDING CODE THE DESIGNER OF |
| | RECORD WILL NEED TO CLARIFY HOW THE PLANS WERE |
| | DEVELOPED FBC-EXST. BLDG. CODE 301.1 ALSO REVIEW |
| | 1001.3.1 PARTIAL CHANGE OF OCCUPANCY CLASSIFICATION. |
| | WHERE A PORTION OF AN EXISTING BUILDING IS CHANGED TO A |
| | NEW OCCUPANCY CLASSIFICATION, SECTION 1012 SHALL APPLY. |
| | |
| | |
| | 1012.1.2 FIRE PROTECTION AND INTERIOR FINISH. |
| | THE PROVISIONS OF SECTIONS 1012.2 AND 1012.3 FOR FIRE |
| | PROTECTION AND INTERIOR FINISH, RESPECTIVELY, SHALL |
| | APPLY TO ALL BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY |
| | CLASSIFICATION |
| | |
| | 1012.2 FIRE PROTECTION SYSTEMS. |
| | FIRE PROTECTION SYSTEMS SHALL BE PROVIDED IN ACCORDANCE |
| | WITH SECTIONS 1012.2.1 AND 1012.2.2. |
| | |
| | 1012.2.1 FIRE SPRINKLER SYSTEM. |
| | WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT |
| | REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE |
| | PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH |
| | CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH |
| | SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE |
| | CHANGE OF OCCUPANCY OCCURS. |
| | |
| | 1012.2.2 FIRE ALARM AND DETECTION SYSTEM. |
| | WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT |
| | REQUIRES A FIRE ALARM AND DETECTION SYSTEM TO BE |
| | PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH |
| | CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH |
| | SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE |
| | CHANGE OF OCCUPANCY OCCURS. EXISTING ALARM NOTIFICATION |
| | APPLIANCES SHALL BE AUTOMATICALLY ACTIVATED THROUGHOUT |
| | THE BUILDING. WHERE THE BUILDING IS NOT EQUIPPED WITH A |
| | FIRE ALARM SYSTEM, ALARM NOTIFICATION APPLIANCES SHALL |
| | BE PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF |
| | OCCUPANCY OCCURS AND SHALL BE AUTOMATICALLY ACTIVATED. |
| | |
| | |
| | 2A) SHEET A1 VERSES THE SHEET M1. THE MEZZANINE |
| | STAIRWELL MID LEVEL APPEARS TO HAVE MECHANICAL |
| | EQUIPMENT. PLEASE PROVIDE CODE COMPLIANCE OF 1 HOUR |
| | 1009.9.3 ENCLOSURES UNDER INTERIOR STAIRWAYS. THE WALLS |
| | AND SOFFITS WITHIN ENCLOSED USABLE SPACES UNDER |
| | ENCLOSED AND UNENCLOSED STAIRWAYS SHALL BE PROTECTED BY |
| | 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION OR THE |
| | FIRE-RESISTANCE RATING OF THE STAIRWAY ENCLOSURE, |
| | WHICHEVER IS GREATER. ACCESS TO THE ENCLOSED SPACE |
| | SHALL NOT BE DIRECTLY FROM WITHIN THE STAIR ENCLOSURE. |
| | |
| | 2B) SHEET A1 VERSES THE SHEET M1. THE MEZZANINE |
| | STAIRWELL MID LEVEL APPEARS TO HAVE MECHANICAL |
| | EQUIPMENT.THE PLANS ARE NOT CLEAR AS TO THE EAST WALL |
| | MID LANDING WHERE THE MECHANICAL SHEETS SHOW VERTICAL |
| | A/C DUCTS. IS THIS A WALL SEPERATING THE MECHANICAL |
| | DUCTWORK FROM THE STIRWELL? 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |