Date Text
2015-11-18 15:49:24 
  
 FROM PREVIOUS LIST:
 3. PG E04.01 THOUGH ALL FIRE ALARM WORK SHALL BE UNDER
 A SEPARATE PERMIT, THE FIRE ALARM CONTROL PANEL
 INDICATED ON THE PLANS SHALL BE PROTECTED WITH A SMOKE
 DETECTOR.
  
 4. PG E05.01 SHOWS AN ELECTRICAL PANEL BUT FAILS TO
 INDICATE THE ILLUMINATION REQUIRED BY NEC 110.26(D).
  
 5. NEC 215.5: YOU SHALL PROVIDE A FEEDER DIAGRAM
 INCLUDING SITE SPECIFIC LOAD CALCS AND CONDUCTOR
 SIZING. INCLUDE THE LOCATION OF ALL PANELS INDICATED.
  
 6. NEC 408.4: YOU SHALL PROVIDE A CIRCUIT DIRECTORY AND
 SHALL MARK ALL APPLICABLE ELECTRICAL PANELS WITH THE
 LOCATION OF THE POWER SOURCE AND DISCONNECT.
  
 7. FBC E SECTION C405 HAS MANDATORY LIGHTING
 REQUIREMENTS WHICH I FAIL TO SEE ON THE FLOOR PLANS.
  
  
  