| 2015-08-27 10:42:29 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15080631 | | | 8/27/15 | | | | | | 1) CLARIFY IF THE CORRIDOR WALLS ARE FIRE-RATED AT THE | | | LOCATIONS WHERE THE DUCTS ARE MAKING PENETRATIONS. | | | PLEASE NOTE FIRE DAMPERS MAY BE REQUIRED. | | | 2) REFER TO SECTION C101.4.5 FBC-14 ENERGY | | | CONSERVATION: CHANGE IN SPACE CONDITIONING. | | | ANY NONCONDITIONED SPACE THAT IS ALTERED TO BECOME | | | CONDITIONED SPACE SHALL BE REQUIRED TO BE BROUGHT INTO | | | FULL COMPLIANCE WITH THIS CODE. | | | PLEASE PROVIDE TWO SETS OF ENERGY CALCULATIONS FOR THE | | | NEW CONDITIONED ROOMS AND SPACES OF THE BUILDING. | | | 3) SHEET M01.01: THE MINIMUM CHANNEL WIDTH FOR THE DUCT | | | SUPPORT HANGER SPACED 8 FT. O.C. IS 3 INCHES. FOR A 2 | | | INCH HANGER WIDTH THE MAXIMUM SPACING IS 4 FT. SEE | | | CHAPTER 6 SMACNA FIBROUS GLASS DUCT CONSTRUCTION | | | STANDARDS- 2010 AND CORRECT THE DETAIL. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|