2015-08-31 07:45:17 
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15080631
 ADD: 7320 S. DIXIE HWY
 CONT: CAL DEVELOPMENT
 TEL: (954)564-0655
 E-MAIL:[email protected]
  
 2014 FLORIDA BUILDING CODE W
 * 2014WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. AUGUST 31/ 2015
 ACTION: DENIED
  
 1) SHEET A02.01:
  
 1A) DOOR # 100BA NOTE # 2 INDICATES TO INSTALL A NEW
 DOOR IN OPENING. NOTE THIS IS NOT CLEAR IF THE DOOR
 ONLY IS BEING REPLACED OR IF DOOR AND FRAME. DOOR AND
 DOOR FRAME TYPE E2. IF THE DOOR AND FRAME ARE BEING
 REPLACED THE N COMPLIANCE WITH: 2014 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
 1B) 2014 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 1C) EXTERIOR DOOR # 100BA IS BEING REPLACED THEN THE
 WIND DESIGN CRITERIA IS REQUIRED.
 2014 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 1C)(1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 1C)(2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE
 7-10.
  
 1C)(3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 1C)(4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 1C)(5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2) .
  
 1D) NOTE # 07 INDICATES WALL FINISHES COVE BASE, IS
 THIS A NEW WALL? FOR THIS FLOOR THERE IS AREAS LABELED
 UNOCCUPIED OFFICES, THERE STILL SHOULD BE A OCCUPANT
 LOAD ASSIGNED TO THESE AREAS. IN DOING SUCH PLEASE
 PROVIDE WHAT THE OCCUPANT LOAD IS FOR THE SECOND FLOOR.
 2014 FBC-B 302.1.
 ALSO SEE 2014 FBC-B TABLE 1018.1. BUSINESS OCCUPANCY
 >30 NON-SPRINKLERED 1 HR FIRE RATING.
  
 1E) NOTE # 4 INDICATES A NEW PARTITION IN STAIRWELL,
 WALL IDENTIFICATION TAG A3A BUT THERE IS NO SUCH WALL
 TAG FOUND ON SHEET A00.30. NOTE THIS SHOULD BE A FIRE
 RATED PARTITION, STAIRWELLS, 2014 FBC- 1022.2
 CONSTRUCTION.
  
 2) IN STAIRWELL DOOR # 100C THE DOOR SCHEDULE INDICATES
 NOT FIRE RATED. 2014 FBC-B 1022.2 SEE FIRE RATING
 REQUIREMENTS. PLEASE NOTE THIS DOOR SHOULD NOT BE IN
 THE STAIRWELL BUT ACCESSED THROUGH FROM THE EXTERIOR
 SINCE THIS A DOOR TO A STORAQGE ROOM. SEE 1022.5
 PENETRATIONS.
  
 3) NOTE # 8 INDICATES THE USE OF A NEW GUARDRAILS ON
 THE UNENCLOSED STAIR A. PLEASE NOTE THIS GUARDRAIL
 NEEDED TO BE UPDATED BY ONSITE FIRE INSPECTION.
 COMPLIANCE WITH THE 2014 EXISTING BUILDING CODE
 805.10.1 AND 805.10.2. THE DESIGN SHALL BE INSTALLED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE. PLEASE
 REVIEW SECTION 1013.3 & 1013.4 OPENING LIMITATIONS.
 THIS AREA IS A BUSINESS OCCUPANCY AN WILL NEED TO
 COMPLY WITH NOT ALLOWING A 4 INCH SPHERE NO TO PASS
 THROUGH.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  