Plan Review Notes
Plan Review Notes For Permit 15080617
Permit Number 15080617
Review Stop B
Sequence Number 1
Notes
Date Text
2015-08-25 18:45:04****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. REVISE PLAN TO SHOW FIRE RATED WALLS AS WELL AS FIRE
 RATING, FBC 107, FBC 715.4.
  
 2. REVISE PLAN TO INCLUDE THE NUMBER OF STORIES IN THIS
 BUILDING. THREE FLOORS ARE SHOWN ON THE PLAN, BUT
 AERIAL PHOTOGRAPHY APPEARS TO SHOW A FIVE STORY
 BUILDING. A 2 HOUR STAIR EXIT ENCLOSURE IS REQUIRED FOR
 A FIVE STORY BUILDING, 90 MINUTE DOORS REQUIRED, FBC
 TABLE 719.4.
  
 REVISE PLAN TO CLARIFY AND SHOW COMPLIANCE.
  
 3. FOR OUR RECORDS, PROVIDE A COPY OF THE ASBESTOS
 REMOVAL PERMIT.
  
 4. FIRE PLAN REVIEW BY STATE FIRE MARSHALL REQUIRED.
  
  
  
  
  