Plan Review Notes
Plan Review Notes For Permit 15080594
Permit Number 15080594
Review Stop P
Sequence Number 1
Notes
Date Text
2015-08-31 13:12:231ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1.ALL PLUMBING SHALL COMPLY WITH FBC RESIDENCIAL 2014
 5TH ADDTION. .
  
 2.PROVIDE SPECS FOR WATER HEATER AND SHOW LOCATION.
 PER WPB AMENDMENT TO FBC SEC 107.1.2
 3. CLEANOUTS SHALL BE INSTALLED NEAR THE JUNTION OF THE
 BUILDING DRAIN AND BUILDING SEWER . IT DOES NOT CLEARLY
 INDICATE THIS ON THE RISER DIAGRAM ON M.01 PLEASE
 CLARIFY.
 FBC RES SEC P3005.2.7
 4. SHEET M.01 PLUMBING RISER DOES NOT SHOW VENT FOR
 WASHING MACHINE.MUST SHOW VENT TO COMPLY WITH.
 FBC RES. P3101.2
 5.A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECTS THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.