| Plan Review Notes For Permit 15080594 |
| Permit Number |
15080594 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-08-31 13:12:23 | 1ST REVIEW: FBC 2014 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | 561-805-6711 | | | [email protected] | | | | | | | | | PLUMBING COMMENTS: | | | | | | 1.ALL PLUMBING SHALL COMPLY WITH FBC RESIDENCIAL 2014 | | | 5TH ADDTION. . | | | | | | 2.PROVIDE SPECS FOR WATER HEATER AND SHOW LOCATION. | | | PER WPB AMENDMENT TO FBC SEC 107.1.2 | | | 3. CLEANOUTS SHALL BE INSTALLED NEAR THE JUNTION OF THE | | | BUILDING DRAIN AND BUILDING SEWER . IT DOES NOT CLEARLY | | | INDICATE THIS ON THE RISER DIAGRAM ON M.01 PLEASE | | | CLARIFY. | | | FBC RES SEC P3005.2.7 | | | 4. SHEET M.01 PLUMBING RISER DOES NOT SHOW VENT FOR | | | WASHING MACHINE.MUST SHOW VENT TO COMPLY WITH. | | | FBC RES. P3101.2 | | | 5.A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL | | | PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT | | | THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE | | | REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK. | | | PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT | | | SPECIFICATIONS AND GAS RISER THAT REFLECTS THE ENTIRE | | | SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC. | | | 107.2.1. |
|