| 2015-09-30 13:58:21 | RESIDENTIAL (R3) ADDITION/ALTERATION MECHANICAL REVIEW |
| | COMMENTS. |
| | CODE: FBC-5TH EDITION (2014) |
| | |
| | 1- PROVIDE EQUIPMENT SIZING CALCULATIONS (2 COPIES) |
| | THAT COMPLY WITH SEC. R403.6.1 OF FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | NOTE: COORDINATE WITH THE ENERGY CALCULATIONS SUBMITTED |
| | TO AVOID CONFLICTS. |
| | |
| | 2- SHEET M.01: |
| | A) THE A/C MANUFACTURER AND MODEL NUMBER LISTED ON THE |
| | EQUIPMENT SIZING CALCULATIONS TO BE LISTED ON THE A/C |
| | PLAN. SEC. 107.5.3(10) OF CITY AMENDMENTS. |
| | |
| | B) LOCATION OF RETURN AIR GRILLES BY THE KITCHEN AREA |
| | ARE NOT ALLOWED. SEC. M1602.2 OF FBC-RESIDENTIAL, 5TH |
| | EDITION (2014). REVISE AS REQUIRED. |
| | |
| | C) SHOW DUCTWORK FOR RETURN AIR GRILLES. AND, SPECIFY |
| | SIZE. SEC. M1602.4 OF FBC-RESIDENTIAL, 5TH EDITION |
| | (2014). |
| | |
| | D) SPECIFY ALL CFM'S FOR EACH ROOM . SEC. 107.5.3(10) |
| | OF CITY AMENDMENTS. |
| | |
| | E) PLAN TO SHOW COMPLIANCE WITH THE MECHANICAL |
| | VENTILATION AS REQUIRED BY SEC. M1507 AND TABLE M1507.4 |
| | OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | NOTE: PROPOSED LOCATION FOR THE A/C COMPRESSOR MAY NOT |
| | BE ALLOWED BY ZONING. IT'S ENCROACHING INTO THE |
| | SETBACKS. COORDINATE LOCATION WITH ZONING TO AVOID |
| | CONFLICTS. |
| | |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE REPLACE AND REMOVED ANY REVISED DRAWINGS. |
| | SUBMIT OLD COPIES FOR REFERENCE. |
| | |