2015-09-30 13:58:21RESIDENTIAL (R3) ADDITION/ALTERATION MECHANICAL REVIEW
 COMMENTS.
 CODE: FBC-5TH EDITION (2014)
  
 1- PROVIDE EQUIPMENT SIZING CALCULATIONS (2 COPIES)
 THAT COMPLY WITH SEC. R403.6.1 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
 NOTE: COORDINATE WITH THE ENERGY CALCULATIONS SUBMITTED
 TO AVOID CONFLICTS.
  
 2- SHEET M.01:
 A) THE A/C MANUFACTURER AND MODEL NUMBER LISTED ON THE
 EQUIPMENT SIZING CALCULATIONS TO BE LISTED ON THE A/C
 PLAN. SEC. 107.5.3(10) OF CITY AMENDMENTS.
  
 B) LOCATION OF RETURN AIR GRILLES BY THE KITCHEN AREA
 ARE NOT ALLOWED. SEC. M1602.2 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014). REVISE AS REQUIRED.
  
 C) SHOW DUCTWORK FOR RETURN AIR GRILLES. AND, SPECIFY
 SIZE. SEC. M1602.4 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 D) SPECIFY ALL CFM'S FOR EACH ROOM . SEC. 107.5.3(10)
 OF CITY AMENDMENTS.
  
 E) PLAN TO SHOW COMPLIANCE WITH THE MECHANICAL
 VENTILATION AS REQUIRED BY SEC. M1507 AND TABLE M1507.4
 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 NOTE: PROPOSED LOCATION FOR THE A/C COMPRESSOR MAY NOT
 BE ALLOWED BY ZONING. IT'S ENCROACHING INTO THE
 SETBACKS. COORDINATE LOCATION WITH ZONING TO AVOID
 CONFLICTS.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REPLACE AND REMOVED ANY REVISED DRAWINGS.
 SUBMIT OLD COPIES FOR REFERENCE.
  