| Plan Review Notes For Permit 15080594 |
| Permit Number |
15080594 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-10-01 18:05:40 | 1ST REVIEW: FBC 2014 5TH ED. | | | | | | UPDATE PLAN TO DEMONSTRATE COMPLIANCE WITH THE | | | FOLLOWING: | | | | | | FBC- 107.3.5.3 ? PROVIDE A PANEL SCHEDULE TO SHOW | | | CIRCUITS, WIRING METHOD, WIRE SIZE, OCP, ECT., SHOW | | | DISCONNECTS AT EQUIPMENT WHERE REQUIRED. SHOW EXTERIOR | | | OUTLETS TO BE GFI. SHOW ADDITIONAL SMOKE DETECTOR | | | OUTSIDE OF BEDROOM (FBC-R 314.3.1 ) AND CARBON DIOXIDE | | | DECTOR (FBC-R 315.1 ) IF RANGE IS GAS AS REQUIRED. | | | | | | INDICATE CODE VERSION IN EFFECT, REFERENCE APPLICABLE | | | CODE, SEE BUILDING REVIEWER COMMENT. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|