2015-09-29 10:42:37RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE: FBC-5TH EDITION (2014)
  
 1- CURRENT CODE IN EFFECT IS THE FBC-5TH EDITION (2014)
 NOT 2010 FBC. UPDATE ALL PLANS AND ALL NOTES AS
 REQUIRED. CHAPTER 553 F.S.
  
 2- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 THEN BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 3- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 908
 OF FBC-EXISTING BUILDING, 5TH EDITION (2014).
 NOTE: COORDINATE ALL INFORMATION WITH ARCHITECTURAL
 PLANS TO AVOID CONFLICTS OR DELAYS.
  
 4- SHEET A.01:
 A) ALTERATION LEVEL SPECIFIED IS INCORRECT. SEE SEC.
 505 OF FBC-EXISTING BUILDING, 5TH EDITION (2014) AND
 REVISE AS REQUIRED. THIS IS ALTERATION LEVEL 3 PLUS
 ADDITION. SQUARE FOOTAGE WAS ADDED TO THE EXISTING
 BUILDING. THE PROPERTY APPRAISER ACTUAL SQUARE FOOTAGE
 IS 594 S.F. ( 502 S.F. FOR BASE AREA AND 92 S.F. FOR
 STORAGE). SEE PROPERTY APPRAISER RECORDS. THERE ARE NO
 CITY PERMITS FOR ADDITIONAL WORK ON REAR BUILDING.
  
 B) REVISE DESIGN CRITERIA. REFER TO THE CURRENT 2014
 CODE. CHAPTER 553 F.S.
  
 5- SHEET A.02:
 A) EXTERIOR ELEVATIONS SHOWN ON SHEET A.02 DON'T MATCH
 EXTERIOR ELEVATIONS SHOWN ON SHEET A.04. PROVIDE ONLY
 ONE DRAWING WITH PROPOSED EXTERIOR ELEVATIONS THAT
 MATCHES PROPOSED FLOOR PLAN TO AVOID CONFLICTS. SEC.
 107.2.1 CITY AMENDMENTS.
  
 B) REVISE WINDOWS AND DOORS DESIGN PRESSURES
 INFORMATION:
 (1) BUILDING IS LOCATED IN EXPOSURE "C" NOT "B" . SEC.
 R301 OF FBC-RESIDENTIAL, 5TH EDITION (2014)
  
 (2) REVISE DESIGN PRESSURES TO CORRESPOND TO EXPOSURE
 "C" AND ACCORDING TO THE BUILDING HEIGHT AND LOCATION
 (END OR INTERIOR ZONE). SEC. R301 OF FBC-RESIDENTIAL,
 5TH EDITION (2014)
  
 (3) REFER TO THE CURRENT 2014 CODE. CHAPTER 553 F.S.
  
 6- SHEET A.03:
 A) NOTES ON THIS SHEET DON'T CORRESPOND TO THE TYPE OF
 CONSTRUCTION OF THIS BUILDING. THERE ARE NOT CMU WALLS
 ON THIS BUILDING. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 B) DIMENSIONS SHOWN ON THE "TYP. SECTION DETAIL AT NEW
 CONCRETE SLAB" IS NOT LEGIBLE. REVISE AS REQUIRED. SEC.
 107.2.1 CITY AMENDMENTS.
  
 C) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 16"X16" CORNER FOOTING. SPECIFY CONCRETE PAD DEPTH AND
 REINFORCING. SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 D) WHERE IS THE FOOTING SCHEDULE SPECIFIED ON THE "TYP.
 SECTION DETAIL AT NEW FOOTING IF NONE EXISTING" DETAIL
 . PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 FOOTING SIZE AND REINFORCING. SEC. R301 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 7- SHEET A.04:
 A) PROPOSED SOUTH AND EAST EXTERIOR WALLS NEED TO
 COMPLY WITH TABLE R302.1(1) OF FBC-RESIDENTIAL, 5TH
 EDITION (2014). PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING COMPLIANCE WITH THE FIRE RATING
 OF THE WALLS AND OVERHANGS. ALSO, REVISE OPENINGS IN
 WALLS.
 SEC. 901.2 AND SEC. 701.2 OF FBC-EXISTING BUILDING, 5TH
 EDITION (2014).
  
 B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE TRELLIS SHOWN ON THE EXTERIOR
 ELEVATIONS. SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 C) SPECIFY CARBON MONOXIDE ALARM AS REQUIRED BY SEC.
 R315 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 D) SOUTH ELEVATION IS MISSING THE AIR HANDLER UNIT
 CLOSET EXTERIOR DOOR. SEC. 107.2.1 CITY AMENDMENTS.
  
 8- SHEET A.06: CLEARLY IDENTIFY THE WALL TYPE LEGEND
 AND ALL DETAILS SHOWN ON THIS SHEET WITH FLOOR PLAN
 SHOWN ON SHEET A.04. SEC. 107.2.1 CITY AMENDMENTS.
  
 9- SHEET A.08: DIMENSIONS SHOWN ON THE WALL/BLDG
 SECTIONS ARE NOT LEGIBLE. SEC. 107.2.1 CITY AMENDMENTS.
 CLEARLY SPECIFY THE CLEARANCE DIMENSION FROM FINISH
 GRADE TO FINISH FLOOR AND THE OVERHANG DIMENSION.
  
 10- SHEET S.01:
 A) ROOF FRAMING PLAN: CLEARLY KEY THE CONNECTORS THAT
 ARE LISTED ON THE TRUSS ANCHOR SCHEDULE ON SHEET S.02.
 SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 B) THE BUILDING IS LOCATED IN EXPOSURE "C" NOT "B".
 REVISE WIND INFORMATION AS REQUIRED. SEC. R301 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 C) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 STEEL COLUMN LOCATED AT THE CORNER OF THE BRICK PATIO.
 SPECIFY TOP AND BOTTOM CONNECTORS. SEC. R301 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 D) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 BEAMS AT THE BRICK PATIO. ROOF FRAMING PLAN DOESN'T
 SHOW ANY AND SPECIFY ALL END CONNECTORS. SEC. R301 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 11- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) METAL ROOFING FLORIDA PRODUCT APPROVAL FL17678
 SUBMITTED: (1) CLEARLY MARK WHICH APPROVED ASSEMBLY IS
 GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH SEC.
 R301 OF FBC-RESIDENTIAL, 5TH EDITION (2014). (2) PAGES
 SHOWING THE APPROVED ASSEMBLIES ARE INCOMPLETE.
 INFORMATION ON THE RIGHT HAND SIDE IS MISSING. PROVIDE
 COMPLETE UN-CUT PAGES. NOTE: MAKE COPIES ON LANDSCAPE
 FORMAT TO GET COMPLETE PAGE.
  
 B) FRENCH DOORS NOA 12-0516.02 SUBMITTED: PAGES SHOWING
 THE DOOR DRAWINGS ARE INCOMPLETE. PROVIDE COMPLETE
 UN-CUT PAGES. NOTE: MAKE COPIES ON LANDSCAPE FORMAT TO
 GET COMPLETE PAGE.
  
 C) SINGLE HUNG WINDOWS NOA 11-1013.14 SUBMITTED: PAGES
 SHOWING THE DOOR DRAWINGS ARE INCOMPLETE. PROVIDE
 COMPLETE UN-CUT PAGES. NOTE: MAKE COPIES ON LANDSCAPE
 FORMAT TO GET COMPLETE PAGE.
  
 D) HARDI-BOARD SIDING AS SHOWN ON PLANS.
  
 E) WINDOW MULLIONS AS SHOWN ON PLANS FOR NEW MASTER
 BATHROOM.
  
 F) ENTRY DOOR AS SHOWN ON PLANS.
  
 G) AHU CLOSET EXTERIOR DOOR AS SHOWN ON PLANS.
  
 H) ALL SIMPSON AND USP STRUCTURAL CONNECTORS SPECIFIED
 ON PLANS AND ALL DETAILS. PROVIDE ONLY THE FLORIDA
 PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING THE
 SPECIFIED CONNECTOR OR DESIGN PROFESSIONAL TO LIST THE
 FLORIDA PRODUCT APPROVAL NEXT TO EACH SPECIFIED
 CONNECTOR. NOTE: SOME PRODUCT APPROVAL SPECIFIED ON
 PLANS (TRUSS ANCHOR SCHEDULE) DON'T CORRESPOND TO THE
 CURRENT 2014 CODE. REVISE THEM AS REQUIRED ALSO.
  
 12- ARCHITECT OF RECORD TO APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 13- PROVIDE CURRENT ICC EVALUATION REPORT (2 COPIES)
 FOR THE ICYNENE INSULATION SPECIFIED ON PLANS. SEC.
 R316 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
  
 NOTE: IF THERE ARE TWO UNITS IN THE MAIN HOUSE. THEN
 NEED PERMITS AN PLANS TO CONVERT IT BACK TO ONE UNIT AS
 ORIGINALLY APPROVED FOR. SEE ZONING COMMENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REPLACE AND REMOVED ANY REVISED DRAWINGS.
 SUBMIT OLD COPIES FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712