| 2015-09-09 07:57:51 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15080551 |
| | ADD: 600 OKEECHOBEE BLVD. |
| | CONT: COASTAL CONSTRUCTION |
| | TEL: (561)659-5819 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION, |
| | |
| | 1ST REVIEW |
| | DATE: WED. SEPT. 09/2015 |
| | ACTION: DENIED |
| | |
| | 1) SHEET LS 503_LD |
| | 1A) THERE IS NO WIND DESIGN FOR THIS 10 FT. HIGH CMU |
| | SCREEN WALL. |
| | 2014 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCERESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | 1.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| | VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 1609.3.1. |
| | |
| | 1.2. RISK CATEGORY. |
| | |
| | 1.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. |
| | |
| | 1.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 1.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF |
| | (KN/M2). |
| | |
| | 2) SHEET LS 503_LD NOTE # 1 INDICATES WALL & FOOTING |
| | WALL DESIGN ENGINEERED BY OTHERS, NO STRUCTURAL SHEETS |
| | WERE SUBMITTED UNDER THIS |
| | REVIEW. PLEASE NOTE THE FOLLOWING DESIGN CRITERIA, 2014 |
| | FBC-B: |
| | |
| | 1807.2.3 SAFETY FACTOR. RETAINING WALLS SHALL BE |
| | DESIGNED TO RESIST THE LATERAL ACTION OF SOIL TO |
| | PRODUCE SLIDING AND OVERTURNING WITH A MINIMUM SAFETY |
| | FACTOR OF 1.5 IN EACH CASE. THE LOAD COMBINATIONS OF |
| | SECTION 1605 SHALL NOT APPLY TO THIS REQUIREMENT. |
| | INSTEAD, DESIGN SHALL BE BASED ON 0.7 TIMES NOMINAL |
| | EARTHQUAKE LOADS, 1.0 TIMES OTHER NOMINAL LOADS, AND |
| | INVESTIGATION WITH ONE OR MORE OF THE VARIABLE LOADS |
| | SET TO ZERO. THE SAFETY FACTOR AGAINST LATERAL SLIDING |
| | SHALL BE TAKEN AS THE AVAILABLE SOIL RESISTANCE AT THE |
| | BASE OF THE RETAINING WALL FOUNDATION DIVIDED BY THE |
| | NET LATERAL FORCE APPLIED TO THE RETAINING WALL. |
| | EXCEPTION: WHERE EARTHQUAKE LOADS ARE INCLUDED, THE |
| | MINIMUM SAFETY FACTOR FOR RETAINING WALL SLIDING AND |
| | OVERTURNING SHALL BE 1.1. |
| | |
| | 1807.2.4 REINFORCED MASONRY RETAINING WALLS. VERTICAL |
| | REINFORCEMENT FOR MASONRY RETAINING WALLS SHALL COMPLY |
| | WITH TABLE 1807.2.4 OR SHALL BE DESIGNED IN ACCORDANCE |
| | WITH TMS 402/ACI 530/ASCE 5. MASONRY SHALL BE FULLY |
| | GROUTED WITH A MINIMUM F"M OF 1,500 PSI (10 343 KPA). |
| | MORTAR FOR MASONRY SHALL BE TYPE M OR S AND LAID IN |
| | RUNNING BOND. THE SPECIFIED LOCATION OF THE |
| | REINFORCEMENT SHALL EQUAL OR EXCEED THE EFFECTIVE DEPTH |
| | DISTANCE, D, NOTED IN TABLE 1807.2.4 AND SHALL BE |
| | MEASURED FROM THE EXPOSED SIDE OF THE WALL TO THE |
| | CENTER OF THE VERTICAL REINFORCEMENT. FOOTINGS FOR |
| | REINFORCED MASONRY RETAINING WALLS SHALL BE DESIGNED IN |
| | ACCORDANCE WITH ACI 318. |
| | |
| | 3) SHEET LS 503_LD NOTE # 2 INDICATES THE USE OF COLD |
| | APPLIED WATERPROOFING MEMBRANE TO WALL BELOW GRADE. |
| | 2014 FBC-B 1805.3.2 WALLS. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |