| 2015-09-26 09:24:18 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15080547 |
| | ADD: 550 S. ROSEMARY AVE. #160 |
| | CONT: DC GREEN, LLC |
| | TEL: (772)919-1412 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W * 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION, |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: SAT. SEPT. 26/2015 |
| | ACTION: PROVISO/ RED LINED |
| | |
| | 1A) S HEET A130.1 EXTERIOR WALLS SHOW A WALL TAG # 1. |
| | WALL IDENTIFICATION TAGS FOUND ON SHEET A020.1 AND |
| | REFERENCES DETAILS 3 & 4 SHEET A400.2. PLEASE NOTE |
| | THERE ARE 2 ISSUES WITH THIS DETAIL. THE BUILDING IS |
| | CLASSIFIED AS A BUILDING TYPE IB WHICH DOES NOT ALLOW |
| | EXTERIOR PLYWOOD. PLEASE REVIEW 2014 FBC-B 603.1.1.3. |
| | FIRE RETARDANT TREATED WOOD CAN BE USED IN NON-BEARING |
| | EXTERIOR WALLS. |
| | |
| | 1B) DETAILS 3 & 4 ON SHEET A400.2 INDICATE THE USE OF |
| | 30 LB. FELT. PLEASE SEE 2014 FBC-B SECTION 2510.6 WHERE |
| | APPLIED OVER WOOD-BASED SHEATHING, SHALL INCLUDE A |
| | WATER RESISTIVE VAPOR-PERMEABLE BARRIER WITH A |
| | PERFORMANCE AT LEAST EQUIVALENT TO TWO LAYERS OF GRADE |
| | D PAPER. THE INDIVIDUAL LAYERS SHALL BE INSTALLED |
| | INDEPENDENTLY SUCH THAT EACH LAYER PROVIDES A SEPARATE |
| | CONTINUOUS PLANE AND ANY FLASHING (INSTALLED IN |
| | ACCORDANCE WITH SECTION 1405.4) INTENDED TO DRAIN TO |
| | THE WATER-RESISTIVE BARRIER IS DIRECTED BETWEEN THE |
| | LAYERS. |
| | |