| | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15080547 |
| | ADD: 550 S. ROSEMARY AVE. #160 |
| | CONT: DC GREEN, LLC |
| | TEL: (772)919-1412 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W * 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION, |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: WED. SEPT. 23/2015 |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. PLANS WERE NOT STAMPED REVIEWED BY CITY |
| | PLACE MANAGEMENT THEY WERE REVIEWED AND APPROVED. |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 2) COMPLIED. PERMIT # 15051261 INTERIOR- DEMO. THERE IS |
| | NO DEMOLISION PLANS INDICATING WHAT IS BEING DEMOED OR |
| | CHANGED, IS EVERYTHING TO BE CONSIDERED NEW? |
| | 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL |
| | BUILDINGS. FROM THE LAST KNOWN PERMIT 13010420 THERE IS |
| | ALOT OF INTERIOR CHANGES FROM THE LAST KNOWN USE AS FAR |
| | AS LAY OUT AND LIFE SAFETY PLAN. A THOROUGH REVIEW |
| | CANNOT BE MADE AT THIS TIME, AS A RESULT OF THE |
| | ADDITIONAL INFORMATION REQUESTED ADDITIONAL COMMENTS |
| | MAY APPEAR THAT WERE NOT PART OF THIS REVIEW. |
| | |
| | 3) FOR THE AMOUNT OF CHANGES SEEN FROM THE LAST PERMIT |
| | (13010420) AND THE PROPOSED LAYOUT THE PERMIT VALUE |
| | ASSOCIATED WITH THIS DESIGN IS CONSIDERABLY |
| | LOW,EXTREMELY LOW. PERMIT FEES/ PLAN REVIEW: |
| | W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT |
| | FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, |
| | MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS |
| | REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID |
| | AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE |
| | ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY. |
| | |
| | 108.3* BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 4) 2ND REQUEST. SHEET A120.1THE MENS RESTROOM APPEARS |
| | TO HAVE BEEN RENOVATED WITH THE RELOCATION OF THE ENTRY |
| | WALL OF THE RESTROOM. THE NEW PLANS SHOW THE SAME |
| | ORIGINAL 4 LAVATORIES AND A LONGER COUNTER TOP. NO WALL |
| | TAG IDENTIFYING THE WALL TYPE IS PROVIDED ON THE PLANS. |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 5-6) COMPLIED. |
| | |
| | 6A) 2ND REQUEST. RESPONSE INDICATES AREA TO BE |
| | REWORKED. PLEASE NOTE ON SHEET A130.1 EXTERIOR WALLS |
| | SHOW A WALL TAG # 1. WALL IDENTIFICATION TAGS FOUND ON |
| | SHEET A020.1 AND REFERENCES DETAILS 3 & 4 SHEET A400.2. |
| | PLEASE NOTE THERE ARE 2 ISSUES WITH THIS DETAIL. THE |
| | BUILDING IS CLASSIFIED AS A BUILDING TYPE IB WHICH DOES |
| | NOT ALLOW EXTERIOR PLYWOOD. PLEASE REVIEW 2014 FBC-B |
| | 603.1.1.3. FIRE RETARDANT TREATED WOOD CAN BE USED IN |
| | NON-BEARING EXTERIOR WALLS. |
| | |
| | 6B) DETAILS 3 & 4 ON SHEET A400.2 INDICATE THE US OF 30 |
| | LB. FELT. PLEASE SEE 2014 FBC-B SECTION 2510.6 WHERE |
| | APPLIED OVER WOOD-BASED SHEATHING, SHALL INCLUDE A |
| | WATERRESISTIVE VAPOR-PERMEABLE BARRIER WITH A |
| | PERFORMANCE AT LEAST EQUIVALENT TO TWO LAYERS OF GRADE |
| | D PAPER. THE INDIVIDUAL LAYERS SHALL BE INSTALLED |
| | INDEPENDENTLY SUCH THAT EACH LAYER PROVIDES A SEPARATE |
| | CONTINUOUS PLANE AND ANY FLASHING (INSTALLED IN |
| | ACCORDANCE WITH SECTION 1405.4) INTENDED TO DRAIN TO |
| | THE WATER-RESISTIVE BARRIER IS DIRECTED BETWEEN THE |
| | LAYERS. |
| | |
| | 1ST REVIEW COMMENT. PLEASE NOTE SHEET A120.1 THE |
| | PROPOSED PLANS SHOW WORK ON THE EAST AND SOUTH OUTSIDE |
| | DINING AREA WITH WALLS MOVED, DOORS OPENINGS BEING |
| | MODIFIED, A NEW OUTSIDE LOUNGE AREA WALLS REMOVED, THE |
| | KITCHEN NEW COOLERS, OLD ONES MOVED BAR LOCATIONS AND |
| | WALLS MOVED ETC.... |
| | |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |