 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15080547
 ADD: 550 S. ROSEMARY AVE. #160
 CONT: DC GREEN, LLC
 TEL: (772)919-1412
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W * 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. SEPT. 23/2015
 ACTION: DENIED
  
 1) COMPLIED. PLANS WERE NOT STAMPED REVIEWED BY CITY
 PLACE MANAGEMENT THEY WERE REVIEWED AND APPROVED.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) COMPLIED. PERMIT # 15051261 INTERIOR- DEMO. THERE IS
 NO DEMOLISION PLANS INDICATING WHAT IS BEING DEMOED OR
 CHANGED, IS EVERYTHING TO BE CONSIDERED NEW?
 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL
 BUILDINGS. FROM THE LAST KNOWN PERMIT 13010420 THERE IS
 ALOT OF INTERIOR CHANGES FROM THE LAST KNOWN USE AS FAR
 AS LAY OUT AND LIFE SAFETY PLAN. A THOROUGH REVIEW
 CANNOT BE MADE AT THIS TIME, AS A RESULT OF THE
 ADDITIONAL INFORMATION REQUESTED ADDITIONAL COMMENTS
 MAY APPEAR THAT WERE NOT PART OF THIS REVIEW.
  
 3) FOR THE AMOUNT OF CHANGES SEEN FROM THE LAST PERMIT
 (13010420) AND THE PROPOSED LAYOUT THE PERMIT VALUE
 ASSOCIATED WITH THIS DESIGN IS CONSIDERABLY
 LOW,EXTREMELY LOW. PERMIT FEES/ PLAN REVIEW:
 W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 4) 2ND REQUEST. SHEET A120.1THE MENS RESTROOM APPEARS
 TO HAVE BEEN RENOVATED WITH THE RELOCATION OF THE ENTRY
 WALL OF THE RESTROOM. THE NEW PLANS SHOW THE SAME
 ORIGINAL 4 LAVATORIES AND A LONGER COUNTER TOP. NO WALL
 TAG IDENTIFYING THE WALL TYPE IS PROVIDED ON THE PLANS.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 5-6) COMPLIED.
  
 6A) 2ND REQUEST. RESPONSE INDICATES AREA TO BE
 REWORKED. PLEASE NOTE ON SHEET A130.1 EXTERIOR WALLS
 SHOW A WALL TAG # 1. WALL IDENTIFICATION TAGS FOUND ON
 SHEET A020.1 AND REFERENCES DETAILS 3 & 4 SHEET A400.2.
 PLEASE NOTE THERE ARE 2 ISSUES WITH THIS DETAIL. THE
 BUILDING IS CLASSIFIED AS A BUILDING TYPE IB WHICH DOES
 NOT ALLOW EXTERIOR PLYWOOD. PLEASE REVIEW 2014 FBC-B
 603.1.1.3. FIRE RETARDANT TREATED WOOD CAN BE USED IN
 NON-BEARING EXTERIOR WALLS.
  
 6B) DETAILS 3 & 4 ON SHEET A400.2 INDICATE THE US OF 30
 LB. FELT. PLEASE SEE 2014 FBC-B SECTION 2510.6 WHERE
 APPLIED OVER WOOD-BASED SHEATHING, SHALL INCLUDE A
 WATERRESISTIVE VAPOR-PERMEABLE BARRIER WITH A
 PERFORMANCE AT LEAST EQUIVALENT TO TWO LAYERS OF GRADE
 D PAPER. THE INDIVIDUAL LAYERS SHALL BE INSTALLED
 INDEPENDENTLY SUCH THAT EACH LAYER PROVIDES A SEPARATE
 CONTINUOUS PLANE AND ANY FLASHING (INSTALLED IN
 ACCORDANCE WITH SECTION 1405.4) INTENDED TO DRAIN TO
 THE WATER-RESISTIVE BARRIER IS DIRECTED BETWEEN THE
 LAYERS.
  
 1ST REVIEW COMMENT. PLEASE NOTE SHEET A120.1 THE
 PROPOSED PLANS SHOW WORK ON THE EAST AND SOUTH OUTSIDE
 DINING AREA WITH WALLS MOVED, DOORS OPENINGS BEING
 MODIFIED, A NEW OUTSIDE LOUNGE AREA WALLS REMOVED, THE
 KITCHEN NEW COOLERS, OLD ONES MOVED BAR LOCATIONS AND
 WALLS MOVED ETC....
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  