| Plan Review Notes For Permit 15080547 |
| Permit Number |
15080547 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-09-11 16:41:18 | PLUMBING COMMENTS: | | | | | | | | | 1. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, | | | (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING | | | AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ? | | | USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE | | | SEC. 402.4.1 | | | 1ST REVIEW: FBC 2014 | | | 2.PLEASE PROVIDE SPEC SHEETS FOR WATER HEATER AND ALL | | | KITCHEN EQUIPMENT. | | | WPB AMEND . SEC. 107.2.1 | | | 3.SHEET P220 KITCHEN EQUPMENT SCHDULE IS CALLING FOR | | | 140* HOT WATER FOR PRE RINSE FAUCETS1.1 -4.1 IT DOES | | | NOT SHOW THAT ON WATER RISER DIAGRAM PLEASE SHOW. | | | WPB AMEND . SEC. 107.2.1 | | | 4.SHEET P222 ON THE WATER RISER THE FIXTURES ARE NOT | | | LABALLED AND THERE IS NO STUB. FOR DISWASHER PLEASE | | | CORRECT. | | | WPB AMEND . SEC. 107.2.1 | | | 5.SHEET P222 WATER RISER PIPING FOR THE PRE RINSE | | | FAUCETS AND DISHWASHER APPEAR SMALL. SHOW FLOW RATE FOR | | | ALL FAUCETS AND DISHWASHER. | | | WPB AMEND . SEC. 107.2.1 | | | 6.SHOW CALC. COMBUSTION AIR FOR GAS EQUIPMENT. | | | WPB AMEND . SEC. 107.2.1 | | | | | | | | | | | | | | | | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|