| Plan Review Notes For Permit 15080547 |
| Permit Number |
15080547 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-08-26 06:50:22 | 1ST REVIEW: FBC 2014 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | 561-805-6711 | | | [email protected] | | | | | | | | | COMMENTS: | | | | | | 1. SCOPE OF WORK UNCLEAR PLEASE CLARIFY. ARE BATHROOMS | | | EXISTING WITH NO CHANGES.IS THER ANY CHANGES TO GAS | | | PIPING. ETC. | | | PER WPB AMEND. TO FBC SEC. 107.2.1 | | | 2. SHOW CALCULATIONS FOR GREASE TRAP TO DETERMINE IF | | | EXISTING SIZE IS ADEQUATE FOR NEW FIXTURE DRAINAGE. | | | PER WPB AMEND. TO FBC SEC. 107.2.1.,3 | | | 3.SHEET INDEX SHOWS P222 AS PLUMBING ISOMETRICS SHEET | | | P222 IS MISSING PLEASE PROVIDE, PLUMBING ISOMETRIC | | | DRAWINGS. | | | PER WPB AMEND. TO FBC SEC. 107.3.5.1.3(13) |
|