| 2015-08-18 15:44:19 | 1ST REVIEW: FBC 2014 MECHANICAL |
| | PERMIT #15080547 |
| | 8/18/15 |
| | |
| | 1) REFER TO SECTION 809.1 FBC-14 EXISTING BUILDING CODE |
| | AND PROVIDE VENTILATION CALCULATIONS FOR ALL ROOMS AND |
| | SPACES IN ACCORDANCE WITH TABLE 403.3 FBC-14 |
| | MECHANICAL. INDICATE THE REQUIRED O/A CFM'S AND THE |
| | AMOUNT OF CFM'S BEING PROVIDED BY THE EXISTING |
| | SYSTEM(S). |
| | 2) THE CITY OF WEST PALM BEACH DEVELOPMENT SERVICES |
| | DEPARTMENT REQUIRES SEPARATE PERMITS FOR ALL KITCHEN |
| | HOOD, AND WALK-IN COOLER AND FREEZER INSTALLATIONS- THE |
| | PLAN IS INDICATING BOTH. PLEASE PLACE NOTES ON THE |
| | PLANS ACCORDINGLY. |
| | IN REFERENCE TO THIS PERMIT SET OF PLANS IT IS |
| | NECESSARY TO INDICATE HOW MAKE-UP AIR IS BEING PROVIDED |
| | FOR THE NEW EXHAUST HOOD TO VERIFY PROPER AIR BALANCING |
| | WITHIN THE ALTERED SPACE- REFER TO SECTION 508 FBC-14 |
| | MECHANICAL. |
| | 508.1 MAKEUP AIR. |
| | MAKEUP AIR SHALL BE SUPPLIED DURING THE OPERATION OF |
| | COMMERCIAL KITCHEN EXHAUST SYSTEMS THAT ARE PROVIDED |
| | FOR COMMERCIAL COOKING APPLIANCES. THE AMOUNT OF MAKEUP |
| | AIR SUPPLIED TO THE BUILDING FROM ALL SOURCES SHALL BE |
| | APPROXIMATELY EQUAL TO THE AMOUNT OF EXHAUST AIR FOR |
| | ALL EXHAUST SYSTEMS FOR THE BUILDING. THE MAKEUP AIR |
| | SHALL NOT REDUCE THE EFFECTIVENESS OF THE EXHAUST |
| | SYSTEM. MAKEUP AIR SHALL BE PROVIDED BY GRAVITY OR |
| | MECHANICAL MEANS OR BOTH. MECHANICAL MAKEUP AIR SYSTEMS |
| | SHALL BE AUTOMATICALLY CONTROLLED TO START AND OPERATE |
| | SIMULTANEOUSLY WITH THE EXHAUST SYSTEM. MAKEUP AIR |
| | INTAKE OPENING LOCATIONS SHALL COMPLY WITH SECTION |
| | 401.4. |
| | 508.1.1 MAKEUP AIR TEMPERATURE. |
| | THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE |
| | AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10 |
| | DEGREES F (6 DEGREES C) EXCEPT WHERE THE ADDED HEATING |
| | AND COOLING LOADS OF THE MAKEUP AIR DO NOT EXCEED THE |
| | CAPACITY OF THE HVAC SYSTEM. |
| | 3) SHEET FS500.1: PLEASE PROVIDE DETQILS ON THE PLANS |
| | THAT CORRELATE WITH MECHANICAL NOTE 2. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |