Plan Review Notes
Plan Review Notes For Permit 15080547
Permit Number 15080547
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-08-20 11:05:46THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 1) SHEET A 200.1, THERE IS AN INCORRECT REFERENCE TO
 THE FIRE CODE, FFPC (2010). THE CORRECT CODE REFERENCE
 IS 2012.
  
 2) SHEET A120.1, THE DOOR FROM ROOM 116 (BY THE OFFICE
 114) SHALL SWING IN THE PATH OF EXIT TRAVEL PER NFPA
 101, CHAPTER 7. THE OCCUPANCY OF THE ROOM 116 IS
 GREATER THAN 50.
  
 3) SHEET A 200.1, A LIGHTWEIGHT ROOF AND FLOOR TRUSS
 SIGN SHALL BE INSTALLED PER FL STATUTUE.
  
 PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR
 STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION.
 ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT
 RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES
 HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A
 MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND
 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR.
 THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO
 THE LEFT OF THE MAIN ENTRY DOOR.
 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
  