| 2015-08-26 17:44:49 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE |
| | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. |
| | |
| | 1. PAGE A400.2 DETAILS INDICATE THAT COMMUNICATING |
| | PARTITIONS ARE BEING USED, THEREFORE EVERY ELECTRICAL |
| | OUTLET BOX IN A FIRE RATED WALL SHALL BE PROTECTED WITH |
| | AN APPROVED FIRE STOPPING MATERIAL. |
| | 2. PAGE E100 NOTE 29 SHALL BE CORRECTED TO ADDRESS THE |
| | ABOVE COMMENTS. THE WAY NOTE 29 IS STATED ONLY APPLIES |
| | WHEN USING NON-COMMUNICATING PARTITIONS. |
| | 3. PAGE E120 REVISIT THE EMERGENCY LIGHTING ARRANGEMENT |
| | TO PROVIDE PROPER ILLUMINATION THROUGH OUT UNDER |
| | EMERGENCY CONDITIONS. WALK-IN COOLER & FREEZER SHOULD |
| | HAVE AN EMERGENCY LIGHT INSIDE AS WELL. |
| | 4. PAGE E120 NEC 600.5(A) REQUIRES THAT THERE BE A |
| | DEDICATED SIGN OUTLET ADJACENT TO EVERY PEDESTRIAN |
| | DOOR. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |