Plan Review Notes
Plan Review Notes For Permit 15080531
Permit Number 15080531
Review Stop P
Sequence Number 1
Notes
Date Text
2015-08-21 05:31:571) THE PLANS REFER TO THE 2010 FBC. THE CODE IN EFFECT
 IS THE 2014 FBC. REVISE THE NOTES TO REFLECT THE 2014
 FBC. REFER TO THE INDEX SHEET, EQ-1 (GENERAL NOTES
 #3,4,&5 .
 2) SHTS. P-1 & P-3 - SHOW THE CONTINUATION
 POINTS/TERMINATION POINTS OF ALL LINES ON THE NORTH
 SIDE OF THE STRUCTURE (6"W, 3" COND., 4" S,4"W. ETC)
 THERE IS ALSO WHAT APPEARS TO BE A LONG TRENCH DRAIN
 (4"W) AND ALSO A 4"LINE AND A 2" LINE ENTERING OR
 LEAVING WHAT LOOKS LIKE SOME SORT OF SUMP. CLARIFY
 THESE STRUCTURES AND THE TERMINATION POINTS OF THE
 DRAINS. REFER TO COLUMN LINES 4-5 ON "R" LINE.
 3) SHT. P-7 - DETAIL # 3 - WHERE A FLOOR DRAIN IS
 LOCATED WITHIN AN AREA SUBJECT TO FREEZING, THE WASTE
 LINE SERVING THE FLOOR DRAIN SHALL NOT BE TRAPPED AND
 SHALL INDIRECTLY DISCHARGE INTO A WASTE RECEPTOR
 LOCATED OUTSIDE OF THYE AREA SUBJECT TO FREEZING,
 CLARIFY THIS FOR THIS DETAIL.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  