Plan Review Notes
Plan Review Notes For Permit 15080531
Permit Number 15080531
Review Stop M
Sequence Number 1
Notes
Date Text
2015-08-24 16:16:471ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15080531
 8/24/15
  
 1) THE PLANS SHALL BE DESIGNED IN ACCORDANCE WITH THE
 FIFTH EDITION 2014 FLORIDA BUILDING CODES. PLEASE
 REVIEW AND UPDATE THE CODE REFERENCES LISTED ON THE
 COVER SHEET.
 2) SHEET M-1: PROVIDE DEMOLITION NOTES AT THE EXPANDED
 PHARMACY AND THE ENTRANCE TO CLARIFY THE SCOPE OF WORK
 AT EACH LOCATION.
 3) M-2: AC LOAD CALCULATIONS ARE REQUIRED FOR THE NEW
 PHARMACY AC SYSTEM- REFER TO SECTION C403.2.1 FBC-14
 ENERGY CONSERVATION- CALCULATION OF HEATING AND COOLING
 LOADS.
 DESIGN LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE
 PROCEDURES DESCRIBED IN THE ASHRAE/ACCA STANDARD 183 OR
 ACCA MANUAL N AND SHALL BE ATTACHED TO THE CODE
 COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT
 WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE
 MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE
 SIZING CALCULATION SHALL BE SUBMITTED WITH THE
 APPLICATION FOR THE MECHANICAL PERMIT. HEATING AND
 COOLING LOADS SHALL BE ADJUSTED TO ACCOUNT FOR LOAD
 REDUCTIONS THAT ARE ACHIEVED WHEN ENERGY RECOVERY
 SYSTEMS ARE UTILIZED IN THE HVAC SYSTEM IN ACCORDANCE
 WITH THE ASHRAEHVAC SYSTEMS AND EQUIPMENT HANDBOOK.
 ALTERNATIVELY, DESIGN LOADS SHALL BE DETERMINED BY AN
 APPROVED EQUIVALENT COMPUTATION PROCEDURE, USING THE
 DESIGN PARAMETERS SPECIFIED IN CHAPTER 3.
 4) M-3, S-2: PROVIDE THE WIND LOAD DESIGN CRITERIA ON
 THE PLAN FOR TIE DOWN OF THE ROOF TOP AC EQUIPMENT-
 REFER TO SECTION 301.15 FBC-14 MECHANICAL AND SECTION
 1609 FBC-14 BUILDING. PROVIDE SUBMITTALS FOR CURB
 ADAPTERS AND STANDS.
 5) PROVIDE PRIMARY AND SECONDARY CONDENSATE DISPOSAL
 PLANS FOR THE NEW AHU-1: SEE SECTION 307 FBC-14
 MECHANICAL.
 6) PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR
 REFRIGERATION AND KITCHEN HOOD AND EXHAUST SYSTEMS.
 7) REFER TO SECTION C408 (SYSTEM COMMISSIONING) FBC-14
 ENERGY CONSERVATION: PLEASE REVIEW ALL SUB-SECTIONS AND
 PROVIDE A COMMSSIONING PLAN IN ACCORDANCE WITH SECTION
 C408.2.1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  